Configuration
4.8 OPC UA
SIMATIC CC7
74
Operating Instructions, 10/2019, C79000-G8976-C503-02
4.8.4
Properties of the OPC UA server
Identification and addressing
The following addressing and identification features of the OPC UA server of the gateway
apply.
●
Application name, Application URI, Server URL, Port number of the application:
–
See section OPC UA server (Page 68).
●
Namespace of the gateway data points:
–
CC7
●
NodeID - Identifier:
The identifier of the NodeIDs of the data points of the "CC7" namespace is formed by the
server application of the gateway from the CPU name, the data block name and the data
point name:
–
<
CPU name
>.<
DB name
>__<
Data point name
>
Subscriptions
For the number of subscriptions supported by the gateway as OPC UA server for
MonitoredItems, see section Configuration limits - communication (Page 18).
The data management of the subscriptions is stored in the RAM of the gateway.
If there is power down, all data and connection information of subscriptions is lost. After
restarting the server, the client needs to re-establish the connection and set up the
subscriptions again.
Deadband
When monitoring items in the "DataChangeFilter", the OPC UA server of the gateway uses
the filter "AbsoluteDeadband".
Содержание 6GK1411-1AC00
Страница 10: ...Table of contents SIMATIC CC7 10 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 30: ...LEDs Connectors Buttons CLP 2 4 CLP Slot SIMATIC CC7 30 Operating Instructions 10 2019 C79000 G8976 C503 02 ...
Страница 136: ...Dimension drawings SIMATIC CC7 136 Operating Instructions 10 2019 C79000 G8976 C503 02 Figure 8 2 Side view ...
Страница 150: ...Index SIMATIC CC7 150 Operating Instructions 10 2019 C79000 G8976 C503 02 ...