Instructions for fitting connectors, attachments and devices
2.5 Power supply
Passive network components
70
System Manual, 02/2013, C79000-G8976-C282-01
Procedure
Only use cables with the power plug PRO
that meet the following specifications:
Cable diameter
9 ... 13 mm
Cable cross section
mm
2
2.5
1.5
Cable cross section
AWG
10 x 2.2 10 x 1.7
16 A
58 ℃
16 A
45 ℃
Max. current at
ambient temperature
a forcing nut
b sealing ring
c rear wall
d latch
e plug insert
f housing notch
g housing
1.
Thread the forcing nut (a), the
sealing ring (b) and the back wall
(c) loosely over the cable.
13 A
73 ℃
13 A
60 ℃
PIN
PROFINET
1
L1
2
N1
3
L2
4
N2
5
FE
2.
Strip 35 mm of the cable jacket.
3.
With a wire cross section of 2.5
mm² (AWG14), crimp ferrules
DIN 46228-A2.5-10 (dimensions
see figure) to the wire ends. For
a wire cross section of 1.5 mm²
(16 AWG), use the DIN 46228-
A1.5-10 ferrules.
4.
Push the wires into the spring
terminal clamps as shown in the
table.
Remove 10 mm of the insulation from the
es.
wir
5.
Check that good contact is
established by pulling lightly on the
wires.