12.1.4
Shipping and storage conditions
Transport and Storage of Modules
The components described surpass the requirements for transport and storage conditions
according to the following standard:
IEC 61131 Teil 2.
The following information applies to modules transported or stored in their original packaging.
Type of condition
Permitted range
Free fall (in transport packaging)
≤ 0.3 m
Temperature
from -40 °C to + 85 °C
Atmospheric pressure
from 1080 to 660 hPa
(corresponds to an altitude of -1000 to 3500 m)
Relative humidity
of 10 to 95 %, without condensation
Sinusoidal vibrations in accordance with the stand‐
ard:
IEC 60068‑2‑6
5 to 8.4 Hz: 3.5 mm
8.4 to 500 Hz: 9.8 m/s
2
Shock according to IEC 60068-2-29
250 m/s
2
, 6 ms, 1000 shocks
12.1.5
Mechanical and climatic ambient conditions for operation
Conditions of use
The described components are designed for use in a fixed, sheltered location. The operating
conditions exceed the requirements of the following standard:
IEC 61131 Part 2.
The described components meet the operating conditions according to standard:
ISA S71.4 G3
Use with additional measures
The described components must not be operated without additional measures:
● at locations with a high degree of ionizing radiation
● in aggressive environments caused, for example, by
– the development of dust
– corrosive vapors or gases
– strong electric or magnetic fields
● in installations requiring special monitoring, for example
– elevators
– electrical plants in potentially hazardous areas
An additional measure can be installation in a cabinet or in an enclosure, for instance.
Technical data
12.1 General technical data
Compact FF Link
Operating Instructions, 03/2015, A5E35651552-AA
83