Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / BAT1600 / UPS1100
46
Equipment Manual, 07.2021, A5E37775406-11-76
States of the LEDs
Signaling
6EP4132-0JA00-0AY0 (2.5 Ah)
6EP4133-0GA00-0AY0 (3.2 Ah)
6EP4134-0JA00-0AY0 (7.5 Ah)
6EP4135-0GE00-0AY0 (12 Ah)
6EP4137-0GE00-0AX0 (38 Ah)
Off
Module runs up, DC-UPS defective (critical hardware fault)
Flashing green
(0.25/0.25)
Battery is being replaced (button pressed, reset service life)
Flashing green
(1/1)
Battery successfully replaced (LED flashes for 5 s)
Flashing green
(1/1)
Battery replacement recommended (SoH ≤ 20
%)
Green
Battery module OK
Flashing yellow
(0.25/0.25)
End of the battery service life reached (SoH = 0 %) or battery test
negative → battery must be replaced, buffer mode possible
Flashing yellow
(1/1)
Temperature outside the valid range, communication cable interrupted or
different battery types being used → restricted charge operation
Yellow
Selected buffer time cannot be attained
Flashing red (1/1) Battery replacement canceled (LED flashes for 5 s)
Red
Fuse ruptured/not inserted, power cable interrupted, 1 battery in the mod-
ule is not connected, battery pack voltage is not symmetrical or reset button
is pressed > 2 s
2.4.3
SITOP UPS1100
Figure 2-22 Example 6EP4131-0GB00-0AY0
States of the LEDs
Signaling
6EP4131-0GB00-0AY0 (1.2 Ah)
6EP4132-0GB00-0AY0 (2.5 Ah)
6EP4133-0GB00-0AY0 (3.2 Ah)
6EP4133-0JB00-0AY0 (5 Ah)
6EP4134-0GB00-0AY0 (7 Ah)
6EP4135-0GB00-0AY0 (12 Ah)
Off
Module runs up, DC-UPS defective (critical hardware fault)
Green
Battery module OK
Flashing yellow
(1/1)
Battery outside the permitted temperature range
Yellow
Selected buffer time cannot be attained
Red
Battery module fault, maintenance required (incorrect polarity, battery
module not connected, high ohmic battery module connection, battery
deep discharged, fuse defective/ruptured, asymmetrical cell voltage, battery
R test unsuccessful)
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...