Safety, approvals, EMC
9.4 EMC
SITOP UPS1600 / BAT1600 / UPS1100
256
Equipment Manual, 07.2021, A5E37775406-11-76
9.4
EMC
6EP4134-3AB00- … (10 A)
6EP4136-3AB00- … (20 A)
6EP4137-3AB00- … (40 A)
6EP4131-0GB00-0AY0 (1.2 Ah)
6EP4132-0GB00-0AY0 (2.5 Ah)
6EP4133-0GB00-0AY0 (3.2 Ah)
6EP4134-0GB00-0AY0 (7 Ah)
6EP4135-0GB00-0AY0 (12 Ah)
6EP4132-0JA00-0AY0 (2.5 Ah)
6EP4133-0GA00-0AY0 (3.2 Ah)
6EP4134-0JA00-0AY0 (7.5 Ah)
6EP4135-0GE00-0AY0 (12 Ah)
6EP4137-0GE00-0AY0 (38 Ah
)
6EP4133-0JB00-0AY0 (5 Ah)
Electrostatic discharge
EN 61000-4-2 6 kV contact, 8 kV air
5 kV contact, 8 kV air
Electromagnetic fields
EN 61000-4-3 80 - 1000 MHz 10 V/m
1400 - 2000 MHz 10 V/m
2000 - 2700 MHz 10 V/m
895 - 905 MHz and 1.89 GHz 10 V/m
High-speed transient disturbance
variables (burst)
EN 61000-4-4 2 kV at the DC input/output/ BAT power terminals
1 kV at Energy storage link (ESL)
Surge voltages
EN 61000-4-5 500 V symmetrical/unsymmetrical at the DC input/output and BAT
power,
1 kV unsymmetrical at signal connections
0.5 kV at ESL
High-frequency fields
EN 61000-4-6 10 V; 0.15 - 80 MHz
Magnetic fields
EN 61000-4-8 Not applicable
Emitted interference
EN 55022
Class B
Generic standards
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential areas
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...