Technical data
8.7 Mechanical system
SITOP UPS1600 / BAT1600 / UPS1100
246
Equipment Manual, 07.2021, A5E37775406-11-76
8.7
Mechanical system
8.7.1
SITOP UPS1600
6EP4134-3AB00- … (10 A)
6EP4136-3AB00- … (20 A)
… -0AY0
… -1AY0
… -2AY0
… -0AY0
… -1AY0
… -2AY0
Connection system
Screw-type terminal
Connections: DC input
IN+, IN-: 1 screw terminal each for 0.2 - 6 (4) mm² solid (finely stranded)
Connections: DC output
OUT+, OUT-: 1 screw terminal each for 0.2 - 6 (4) mm² solid (finely stranded)
Connections: Battery con-
nection
BAT+, BAT-: 1 screw terminal each for 0.2 - 6 (4) mm² solid (finely stranded)
Connections: Signal con-
nector
X2 (1 - 14): 1 screw terminal each for 0.2 - 1.5 mm² solid/finely stranded
Width of the housing
50 mm
50 mm
50 mm
50 mm
50 mm
50 mm
Height of the housing
138.7 mm
138.7 mm
138.7 mm
138.7 mm
138.7 mm
138.7 mm
Depth of the housing
125 mm
125 mm
125 mm
125 mm
125 mm
125 mm
Installation width
50 mm
50 mm
50 mm
50 mm
50 mm
50 mm
Mounting height
238.7 mm
238.7 mm
238.7 mm
238.7 mm
238.7 mm
238.7 mm
Weight, approx.
0.38 kg
0.4 kg
0.44 kg
0.39 kg
0.41 kg
0.45 kg
Product feature of the hous-
ing:
housing that can be lined
up next to one another
Yes
Type of mounting:
wall mounting
No
Type of mounting:
rail mounting
Yes
Type of mounting:
S7-300 standard rail mount-
ing
No
Mounting
Can be snapped onto standard TH35×7,5/15 mounting rails (EN 60715)
6EP4137-3AB00- … (40 A)
… -0AY0
… -1AY0
… -2AY0
Connection system
Screw-type terminal
Connections: DC input
IN+, IN-: 1 screw terminal each for 0.5 - 16 (4) mm² solid (finely stranded)
Connections: DC output
OUT+, OUT-: 1 screw terminal each for 0.5 - 16 (4) mm² solid (finely stranded)
Connections: Battery con-
nection
BAT+, BAT-: 1 screw terminal each for 0.5 - 16 (4) mm² solid (finely stranded)
Connections: Signal con-
nector
X2 (1 - 14): 1 screw terminal each for 0.2 - 1.5 mm² solid/finely stranded
Width of the housing
70 mm
70 mm
70 mm
Height of the housing
138.7 mm
138.7 mm
138.7 mm
Depth of the housing
150 mm
150 mm
150 mm
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...