Installation
7.9 Service life of the batteries and handling
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
231
7.9.3
Replacing batteries in a battery module
WARNING
The following precautionary measures should be carefully taken into account when working
with the battery module and the batteries:
1.
Remove watches, rings and other metal objects.
2.
Always used tools with insulated handles.
Note
The batteries cannot be replaced for battery modules with LiFePO4 batteries.
The following battery type is used in battery module SITOP BAT1600:
Battery module
Battery types
2.5 Ah device
7.5 Ah device
3.2 Ah device
:
12 Ah device:
38 Ah device:
1 unit
LiFePO4 type: Grepow GRP5970096-25C-25.6V 2800 mAh
3 units
LiFePO4 type: Grepow GRP5970096-25C-25.6V 2800 mAh
2 units
Pb type: YUASA NP3,2-12 or Powerkingdom PS3.2-12
2 units:
Pb type: YUASA NP12-12 or Powerkingdom PS12-12
2 units:
Pb type: YUASA NPL38-12I (FR) or Panasonic P1238APG
Note
In a battery module,
always
replace all batteries.
Always
use the same battery type in a battery module. Before installing new batteries in the
battery module, ensure that all of the batteries have the same charging status.
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...