Engineering and remote access
3.10 OPC UA server
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
177
Display name
Data type
Definition
Description
AlarmLessCapable
ModuleDetected
Boolean
PropertyType
Battery module with reduced power detected.
AlarmMoreCapable
ModuleDetected
Boolean
PropertyType
A battery module with excessive power detected.
AlarmNewBattery
Detected
Boolean
PropertyType
A new battery was connected. The battery will be included in
the calculation of the total capacity and the charge parame-
ters.
AlarmUnexpected
ModuleDetected
Boolean
PropertyType
Unexpected module type detected.
AlarmWrong
BatteryConfiguration
Boolean
PropertyType
Wrong battery configuration
Additional parameters
Display name
Data type
Definition
Description
BatteryModule
IdentNumber
UInt32
PropertyType
Module identification number
DeviceManual
String
PropertyType
Address (path in the file system or URL/web address) of the
operating instructions for the unit.
HardwareRevision
String
PropertyType
Hardware revision of the device
Manufacturer
LocalizedText
PropertyType
Name of the company that manufactured the device
Model
LocalizedText
PropertyType
Model
OrderNumber
String[20]
PropertyType
Article number
RevisionCounter
Int32
PropertyType
Incremental counter that specifies how often the static data
in the device was modified.
SerialNumber
String[16]
PropertyType
ID, which uniquely identifies the device for the device manu-
facturer
SlotId
UInt16
PropertyType
Number of the slot
SoftwareRevision
Integer
PropertyType
Revision status of the device software
VersionNumber
String
PropertyType
Software Version (only SITOP BAT1600)
3.10.6.23
ThirdPartyBatteryParameter
Display name
Data type
Definition
Description
BatteryCapacitySet-
point
Float
AnalogItemType Total capacity of the installed batteries in Ah.
BatteryDefectVoltage
Setpoint
Float
AnalogItemType Voltage value below which a battery is considered to be
defective and should no longer be charged.
BatteryDurationCon-
stantVoltagePhaseSet-
point
UInt16
AnalogItemType Duration of the constant voltage charging phase.
BatteryTypeSetpoint
Byte
PropertyType
Make/type of battery 0 … lead-gel battery (Pb), 1 … pure
lead battery (pPb)
ChargeCurrentSetpoint Float
AnalogItemType Max. permissible current to charge the battery
OperatingTemperature
Setpoint
Sbyte
AnalogItemType Typical ambient temperatures for battery modules in opera-
tion.
StartOfPreserveVoltage
Setpoint
Float
AnalogItemType Threshold when switching over from normal battery charg-
ing to preserve charge voltage (brief post charging).
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...