Engineering and remote access
3.10 OPC UA server
SITOP UPS1600 / BAT1600 / UPS1100
170
Equipment Manual, 07.2021, A5E37775406-11-76
Display name
Data type
Definition
Description
AlarmLow
VoltageMode
Boolean
PropertyType
Input voltage of SITOP UPS1600 is too low. The buffer of the
SITOP UPS1600 is not operational.
AlarmNoCharging
ManualDeactivated
Boolean
PropertyType
Charging function was deactivated by a control command
AlarmOutputTurnedOff Boolean
PropertyType
Output of SITOP UPS1600 has been switched off due to the
execution of a command or because an error situation has
occurred (e.g. temperature or output current too high).
AlarmOutputTurnedOn Boolean
PropertyType
Output of SITOP UPS1600 has been switched on again due
to the execution of a command or because an error situation
has been remedied.
AlarmOverCurrent
Boolean
PropertyType
Output current of SITOP UPS1600 is too high. Output is
switched off for 20 s. The output is switched on again after
20 s.
AlarmResetExecuted
Boolean
PropertyType
Input voltage connected to SITOP UPS1600 was already OK
before the buffer time expired. Connected devices are reset
by switching off the SITOP UPS1600 outputs for the parame-
terized time.
AlarmSurplusBattery
Boolean
PropertyType
More than 6 batteries are connected. Connect max. of
6 batteries to the Energy Storage Link.
AlarmUnknownBattery Boolean
PropertyType
Data from the battery cannot be read correctly. Battery is
defective or not supported by SIEMENS.
AlarmWrongBattery
Polarity
Boolean
PropertyType
Wrong battery polarity - check battery connections.
3.10.6.8
Battery
Display name
Data type
Definition
Description
BatteryCapacity
Setpoint
Float
AnalogItemType Total battery capacity in Ah
BatteryDefectVoltage
Setpoint
Float
AnalogItemType If battery voltage is lower than this value, the battery is con-
sidered defective.
BatteryIgnoreCoding
Setpoint
Boolean
PropertyType
When this parameter is set to '1', data from the coded bat-
tery is ignored. The data is taken from the parameter as-
signment in this case.
BatteryInspection
TimeSetpoint
Byte
PropertyType
Battery test interval in hours
3.10.6.9
Buffering
Display name
Data type
Definition
Description
BufferExpected
CurrentSetpoint
Float
AnalogItemType Estimated average output current during buffer mode
BufferThreshold
Setpoint
Float
PropertyType
Trigger voltage for buffering - buffering is activated below
this value
BufferTime2Setpoint
UInt16
AnalogItemType Additional buffer time after PC shutdown (valid only in con-
junction with SITOP Manager)
BufferTimeSetpoint
UInt16
AnalogItemType Desired buffering time before device switches off
BufferingEnableSet-
point
Boolean
PropertyType
Enable buffering
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...