Engineering and remote access
3.5 SIMATIC STEP 7
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
101
Allocating the SITOP UPS1600 a device name (online)
In order that the configured IO controller can address the SITOP UPS1600, you must assign
each individual IO device (including SITOP UPS1600) the configured device name.
For the procedure described below, the SITOP UPS1600 and the station for the PG/PC must be
accessible online through Ethernet.
1.
Open HW Config.
2.
In the "Target system > Ethernet" menu, click on "Assign device name".
3.
In the "Assign device name" dialog, in the "Device name" field, select SITOP UPS1600.
4.
In the "Available devices" select the SITOP UPS1600. Using the "Flash" button, you can flash
the LED on the SITOP UPS1600 so that the device can be uniquely identified.
5.
Click on the "Assign name" button.
After the name assignment, you can bring the IO controller into the RUN operating state.
When powering up, the IO controller distributes the configuration information to the
SITOP UPS1600 and then goes into cyclic operation.
3.5.6
Diagnostics
The following data can be fetched using the Diagnostics function:
Group
Value
SITOP UPS1600 general
Article number
Serial number
Fetching diagnostics data
You can use the "Station > Open online" menu command in "HW Config" to select the
SITOP UPS1600 and view the diagnostics data.
3.5.7
Firmware update
WARNING
The SITOP UPS1600 is reset while updating the firmware. For safety reasons, the
output is switched off.
Ensure that no damage is caused to the plant or system.
Ensure that the PG/PC and/or all switches, routers and gateways that are used have an
independent power supply during the firmware update.
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...