SITOP PSU6200 3ph
Equipment Manual, 02.2020, A5E44623402-1-76
53
Ambient conditions
8
6EP3433-7SB00-0AX0 (24 V/5 A)
6EP3434-7SB00-3AX0 (24 V/10 A)
6EP3436-7SB00-3AX0 (24 V/20 A)
Ambient temperature
-25 ... 70 °C for natural convection (self convection)
Tested according to:
•
EN 60068-2-1 Cold
•
EN 60068-2-2 Dry heat
•
EN 60068-2-78 Humid heat, constant
•
EN 60068-2-14 Temperature change
Transport and storage temperature
-40 ... 85 °C
Tests (packed for shipping) according to:
•
EN 60068-2-1 Cold
•
EN 60068-2-2 Dry heat
•
EN 60068-2-30 Humid heat, cyclic
Humidity class
Climatic class 3K3 acc. to EN 60721, 5 - 95 % without condensation
Mechanical stressing in operation
Tested according to:
•
EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 – 8.4 Hz
2 g acceleration in the range 8.4 – 150 Hz
•
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms
Damaging gases
Tested according to:
•
EN 60068-2-42 sulfur dioxide
•
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure
Operation:
•
1080 - 795 hPa (0 - 2000 m)
•
For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 4-4 Mounting height derating (Page 24)
•
Overvoltage category:
III to 2000 m (EN 50178)
II from 2000 m to 6000 m (EN 50178)
II to 2000 m (IEC61204-7)
I from 2000 m to 6000 m (IEC61204-7)
Storage:
•
1080 - 660 hPa (0 - 3500 m)
Содержание 6EP3433-7SB00-0AX0
Страница 8: ...Safety instructions SITOP PSU6200 3ph 8 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 22: ...Mounting removal SITOP PSU6200 3ph 22 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 34: ...Installation 5 2 Output side connection SITOP PSU6200 3ph 34 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 48: ...Technical data 6 8 Dimension drawing SITOP PSU6200 3ph 48 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 54: ...Ambient conditions SITOP PSU6200 3ph 54 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 62: ...Environment SITOP PSU6200 3ph 62 Equipment Manual 02 2020 A5E44623402 1 76 ...