Safety, approvals, EMC
7.2 Test voltage
SITOP PSU8200 3ph
Manual, 11.2014, C98130-A7638-A1-2-7629
41
Table 7- 2
Test voltage for 6EP1437-3BA10
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 VDC
2200 VDC
700 VDC
60 s
3000 VAC
1500 VAC
500 VAC
Production test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Field test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA