Technical data
6.4 Closed-loop control
SITOP PSU8200 3ph
Manual, 11.2014, C98130-A7638-A1-2-7629
35
6.4
Closed-loop control
6EP3436-8SB00-0AY0
(24 V/20 A)
6EP1437-3BA10
(24 V/40 A)
Dyn. line regulation (Ue rated ±15 %), max.
1 %
1 %
Dyn. load regulation (Ia: 50/100/50%), Ua ± typ. 2 %
3 %
Load step regulation time 50 to 100 %, typ.
2 ms
-
Load step regulation time 100 to 50 %, typ.
2 ms
-
Regulation time / maximum
10 ms
10 ms
6.5
Protection and monitoring
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V / 40 A)
Output overvoltage protection
< 35 V
< 35 V
Current limitation, typ.
23 A
44 A
Property of the output/short-circuit
proof
Yes
Yes
Short-circuit protection
Optional constant current characteristic curve or latching shutdown
Continuous short-circuit current / rms
value / typical
•
Comment
23 A
Overload capability 150 % Ia rated up
to 5 s/min
44 A
Overload capability 150% Ia rated up to
5 s/min
Overload / short-circuit display
Yellow LED for "overload", red LED for
"latching shutdown"
Yellow LED for "overload", red LED for
"latching shutdown"
6.6
MTBF
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V / 40 A)
Mean Time Between Failures
SN29500: >500000 hours at 40 °C,
rated load, 24-hour operation
SN29500: > 500,000 hours (typ.
700,000 hours) at 40° C, rated load,
24-hour operation
Содержание 6EP1437-3BA10
Страница 8: ...Notes on safety SITOP PSU8200 3ph 8 Manual 11 2014 C98130 A7638 A1 2 7629 ...
Страница 28: ...Installation 5 2 Output side connection SITOP PSU8200 3ph 28 Manual 11 2014 C98130 A7638 A1 2 7629 ...
Страница 38: ...Technical data 6 9 Dimension drawing SITOP PSU8200 3ph 38 Manual 11 2014 C98130 A7638 A1 2 7629 ...
Страница 56: ...Environment SITOP PSU8200 3ph 56 Manual 11 2014 C98130 A7638 A1 2 7629 ...