6.1
Switching cycles
[ID: 80188362763]
Switching capacity and lifetime of the contacts
With an external protective circuit, the contacts will last longer than specified in the table. This
table shows the switching capacity and lifetime of the relay contacts:
Table 6-1
Switching capacity and lifetime of the relay contacts
Resistive load
Voltage
Current
Switching cycles (typi‐
cal)
For resistive load
24 V DC
5.0 A
0.1 million
3.0 A
0.2 million
2.0 A
0.3 million
1.0 A
0.5 million
0.5 A
0.8 million
0.1 A
1 million
48 V DC
2.0 A
0.3 million
1.0 A
0.5 million
0.5 A
0.8 million
0.1 A
1 million
60 VDC
1.0 A
0.5 million
0.5 A
0.8 million
0.1 A
1 million
120 V DC
0.1 A
1 million
For resistive load
48 VAC
to
230 VAC
5.0 A
0.1 million
3.0 A
0.2 million
2.0 A
0.3 million
1.0 A
0.5 million
0.5 A
0.8 million
0.1 A
1 million
With inductive load
24 V DC
2.0 A
0.1 million
1.0 A
0.3 million
0.5 A
0.5 million
0.1 A
1 million
48 V DC
1.0 A
0.3 million
0.5 A
0.5 million
0.1 A
1 million
60 VDC
0.5 A
0.5 million
0.1 A
1 million
120 V DC
0.1 A
1 million
With inductive load
48 V AC
to
230 V AC
2.0 A
0.1 million
1.0 A
0.3 million
0.5 A
0.5 million
0.1 A
1 million
Technical specifications
6.1 Switching cycles
Digital Output Module RQ 4x120VDC-230VAC/5A CO HA (6DL1132-6HD50-0PK0)
26
Manual, 11/2017, A5E39389042-AC