Description
2.4 Selectivity
3VA molded case circuit breakers
56
Manual, 04/2015, A5E03603177010-02
2.4
Selectivity
Switching devices connected in series, e.g. molded case circuit breakers and fuses, work in
a coordinated manner to ensure that switching devices are tripped successively. The closest,
upstream switching device before the location of the short-circuit must trip. The other
switching devices on the same current run do not trip. The purpose of selectivity is to
minimize the effects of a fault in terms of its duration and the area affected by the fault.
Selectivity is achieved when the circuit breakers are matched to each other by means of
selection, configuring and trip settings in such a way that, in the event of a fault, only the
breaker closest to the location of the fault trips.
Short-circuit location
Selective behavior
The selective behavior of molded case circuit breakers is mainly influenced by the following
factors:
●
Tripping value settings of the trip unit
●
Tripping and break times
●
Let-through current values
●
Modes of switching of the relevant circuit breakers
–
Zero-current interrupter
–
Current limiter
Содержание 3VA1 100 A
Страница 1: ......
Страница 2: ......
Страница 71: ...Description 2 6 Protection system 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 71 ...
Страница 94: ...Description 2 8 Electronic trip unit 3VA molded case circuit breakers 94 Manual 04 2015 A5E03603177010 02 ...
Страница 149: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 149 ...
Страница 163: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 163 ...
Страница 354: ...Accessories 4 8 Residual current devices 3VA molded case circuit breakers 354 Manual 04 2015 A5E03603177010 02 ...
Страница 392: ...Accessories 4 10 EFB300 external function box 3VA molded case circuit breakers 392 Manual 04 2015 A5E03603177010 02 ...
Страница 418: ...Accessories 4 14 DIN rail adapter 3VA molded case circuit breakers 418 Manual 04 2015 A5E03603177010 02 ...
Страница 514: ...List of abbreviations C 1 Table of abbreviations 3VA molded case circuit breakers 514 Manual 04 2015 A5E03603177010 02 ...
Страница 518: ...Conversion tables 3VA molded case circuit breakers 518 Manual 04 2015 A5E03603177010 02 ...
Страница 531: ...Index 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 531 ...
Страница 532: ......