Accessories
4.11 Test devices
3VA molded case circuit breakers
404
Manual, 04/2015, A5E03603177010-02
Disconnecting the TD500 from the 3VA2 molded case circuit breaker
1.
Switch off the 3VA2 molded case circuit breaker.
2.
Press the pushbutton labeled <ETU Power ON/OFF>
on the TD500 test device.
The LED labeled "COM" on the TD500 goes out. The ETU is now no longer powered via
the TD500 and is deactivated.
3.
Disconnect the power supply unit from the socket.
4.
Detach the power supply unit cable from the TD500.
5.
Detach the connecting cable between the TD500 and the ETU.
Test tripping functions L, S, I, N and G
1.
Connect the TD500 to the 3VA2 molded case circuit breaker as described above.
2.
Switch on the 3VA2 molded case circuit breaker.
3.
To test the tripping function, press one of the pushbuttons <L>, <S>, <I>, <N> or<G on
the TD500 test device.
–
When a pushbutton is pressed, its LED flashes while the test is in progress.
–
The ETU trips when the set trip times expire and the molded case circuit breaker
switches from "ON" to "TRIP".
–
On completion of the test, the LED of the selected pushbutton changes from flashing
to steady illumination.
4.
Wait for the test to end and evaluate the test result by the status of the LED labeled
"RESULT":
Test was successful:
The LED "RESULT" lights up green.
Test was unsuccessful:
The LED "RESULT" flashes red.
Repeat the test. If the test fails again, contact Technical Support (Page 12) .
5.
Press the pushbutton for the same tripping function again in order to confirm the test
result and restore the TD500 to its initial state.
6.
Switch on the molded case circuit breaker again (ON position) in order to carry out further
tripping function tests.
Содержание 3VA1 100 A
Страница 1: ......
Страница 2: ......
Страница 71: ...Description 2 6 Protection system 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 71 ...
Страница 94: ...Description 2 8 Electronic trip unit 3VA molded case circuit breakers 94 Manual 04 2015 A5E03603177010 02 ...
Страница 149: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 149 ...
Страница 163: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 163 ...
Страница 354: ...Accessories 4 8 Residual current devices 3VA molded case circuit breakers 354 Manual 04 2015 A5E03603177010 02 ...
Страница 392: ...Accessories 4 10 EFB300 external function box 3VA molded case circuit breakers 392 Manual 04 2015 A5E03603177010 02 ...
Страница 418: ...Accessories 4 14 DIN rail adapter 3VA molded case circuit breakers 418 Manual 04 2015 A5E03603177010 02 ...
Страница 514: ...List of abbreviations C 1 Table of abbreviations 3VA molded case circuit breakers 514 Manual 04 2015 A5E03603177010 02 ...
Страница 518: ...Conversion tables 3VA molded case circuit breakers 518 Manual 04 2015 A5E03603177010 02 ...
Страница 531: ...Index 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 531 ...
Страница 532: ......