Description of the individual safety relays
3.6 3TK28 safety relays with relay enabling circuits
3TK28 safety relays
Manual, 07/2016, NEB926157502000/RS-AB/003
59
3TK2821-.C...
3TK2824-.B...
3TK2824-.C...
Design of the electrical connection jumper socket
Yes
Switching capacity current
•
at AC-15 at 24 V
A —
•
of the NO contacts of the relay outputs
–
at AC-15 at 230 V
A 5
6
–
at DC-13 at 24 V
A 5
6
•
of the NC contacts of the relay outputs at
AC-15
–
at 115 V
A 5
—
–
at 230 V
A 5
—
Thermal current of the contact-affected switching
element maximum
A 5
Electrical operating cycles as operating time typical
100 000
Mechanical operating cycles as operating time
typical
10 000 000
Design of the fuse link for short-circuit protection
of the NO contacts of the relay outputs required
gL/gG: 6 A, or quick: 10 A
Type of voltage of the controlled supply voltage
AC/DC
DC
AC/DC
Control supply voltage frequency 1 rated value
Hz 50
—
50
Control supply voltage frequency 2 rated value
Hz 60
—
60
Control supply voltage 1 for DC final rated value
•
for DC rated value
V 24
Operating range factor control supply voltage rated
value of the magnet coil
•
at 50 Hz
–
for AC
0.85
1.1
•
at 60 Hz
–
for AC
0.85
1.1
•
for DC
0.85
1.2