Description of the individual safety relays
3.6 3TK28 safety relays with relay enabling circuits
3TK28 safety relays
Manual, 07/2016, NEB926157502000/RS-AB/003
57
3.6.4.5
Display of the operating state
The operating state and functioning of the device are indicated by three LEDs:
●
POWER
●
CHANNEL 1
●
CHANNEL 2
Operating states of 3TK2821/24
= off
= on
LED
Operation
POWER
CHANNEL 1
CHANNEL 2
Line
supply
EMERGENCY
STOP
ON
Enabling circuit
On
Not pressed
Pressed
Closed
Pressed
Not pressed
Open
Not pressed
Not pressed
Open
Fault
•
Relay welded
•
Motor contactor welded
•
Fault in electronics
Open
Cross-circuit or ground fault in EMERGENCY
STOP circuit (minimum fault current I
Kmin
= 0.5 A;
PTC fuse responds) or no supply voltage
3.6.4.6
State diagrams 3TK2821 / 3TK2824
Figure 3-14 State diagram 3TK2821/24