Description of the individual safety relays
3.6 3TK28 safety relays with relay enabling circuits
3TK28 safety relays
52
Manual, 07/2016, NEB926157502000/RS-AB/003
3TK2822-.....
3TK2823-.....
Design of the electrical connection jumper socket
Yes
Switching capacity current
•
at AC-15 at 24 V
A —
•
of the NO contacts of the relay outputs
–
at AC-15 at 230 V
A 5
–
at DC-13 at 24 V
A 5
•
of the NC contacts of the relay outputs at AC-15
–
at 115 V
A —
–
at 230 V
A —
Thermal current of the contact-affected switching element
maximum
A 5
Electrical operating cycles as operating time typical
100 000
Mechanical operating cycles as operating time typical
10 000 000
Design of the fuse link for short-circuit protection of the
NO contacts of the relay outputs required
gL/gG: 6 A, or quick: 10 A
Type of voltage of the controlled supply voltage
AC/DC
Control supply voltage frequency 1 rated value
Hz 50
Control supply voltage frequency 2 rated value
Hz 60
Control supply voltage 1 for DC final rated value
•
for DC rated value
V 24
Operating range factor control supply voltage rated value
of the magnet coil
•
at 50 Hz
–
for AC
0.85
1.1
•
at 60 Hz
–
for AC
0.85
1.1
•
for DC
0.85
1.2
Содержание 3TK28
Страница 188: ...Mounting 4 4 Disassembling the device 3TK28 safety relays 188 Manual 07 2016 NEB926157502000 RS AB 003 ...
Страница 204: ...Dimension drawings 6 1 Dimension drawings 3TK28 3TK28 safety relays 204 Manual 07 2016 NEB926157502000 RS AB 003 ...
Страница 206: ...Accessories 3TK28 safety relays 206 Manual 07 2016 NEB926157502000 RS AB 003 ...