Functions
6.7 Substation monitoring
Motor
starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
89
6.7.1
Response to residual current detection
If the motor current drops to under 20% from the set operational current or below the
minimum load limit in one of the phases, residual current detection responds. You use this
device parameter to specify how the motor starter is to behave in the event of residual
current being detected:
●
Warning (not in the case of fail-safe motor starters)
●
Tripping
Note
When the motor is switched on, residual current detection is suppressed for approximately
1 s.
Residual current detection for motor starters with 0.1 ... 0.4 A
The following graphic shows the dependence of residual current detection on the set motor
current in the case of motor starters with 0.1 to 0.4 A:
Figure 6-9
Residual current detection 0.1-0.4 A device
Residual current detection for motor starters with 0.3 ... 1 A
The following graphic shows the dependence of residual current detection on the set motor
current in the case of motor starters with 0.3 to 1 A:
Figure 6-10 Residual current detection 0.3-1 A device
Содержание 3RK1308-0 00-0CP0 Series
Страница 1: ...Motor starter 3RK1308 0 00 0CP0 ...
Страница 2: ......
Страница 10: ...Introduction Motor starter 3RK1308 0 00 0CP0 10 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 16: ...Security information Motor starter 3RK1308 0 00 0CP0 16 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 34: ...Documentation guide Motor starter 3RK1308 0 00 0CP0 34 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 174: ...CAx data 10 1 CAx data Motor starter 3RK1308 0 00 0CP0 174 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 204: ...Data sets A 16 I M data Motor starter 3RK1308 0 00 0CP0 204 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...
Страница 218: ...Index Motor starter 3RK1308 0 00 0CP0 218 Equipment Manual 11 2019 A5E34821005002A RS AC 003 ...