Analog value representation
4.4 Effect on analog value representation
2AO U HF analog electronic module (6ES7135-4LB02-0AB0)
Manual, 04/2007, A5E01076940-01
17
Voltage output ranges: 1 to 5 V
Table 4-4
SIMATIC S7 format: Output ranges 1 to 5 V
Units
Output range
1 to 5 V
Decimal
Hexadecimal
Range
0
> 32511
> 7EFF
H
Overflow
5,7000
:
5,0002
32511
:
27649
7EFF
H
:
6C01
H
Overshoot range
5,0000
:
1,0000
27648
:
0
6C00
H
:
0
H
Nominal range
0,9998
:
0
-1
:
-6912
FFFF
H
:
E500
H
Underrange
0
< -6913
< E4FF
H
Underflow
4.4
Effect on analog value representation
4.4.1
Effect of the supply voltage and the operating state on analog output values
The output values of the analog modules are dependent on the supply voltage for
electronics/encoders and on the operating state of the PLC (CPU of the DP master). This is
illustrated by the table below.
Table 4-5
Relationship between the analog output values for the operating state of the PLC (CPU
of the DP master) and the supply voltage L+.
Operating state of the PLC
(CPU of the DP master)
Supply voltage L+ on ET 200S
(power module)
Output value of the electronic
module with analog outputs
PLC values
L+ present
Until first value output:
•
After startup, a signal of 0 mA or
0 V is output.
•
Dependent on the parameter
"CPU/master STOP"
POWER ON RUN
L+ missing
-
L+ present
Dependent on the parameter
"CPU/master STOP"
POWER ON STOP
L+ missing
-
L+ present
Dependent on the parameter
"CPU/master STOP"
POWER OF
F
-
L+ missing
-