2AO U HF analog electronic module (6ES7135-4LB02-0AB0)
Manual, 04/2007, A5E01076940-01
11
Parameters
2
2.1
Parameters
Table 2-1
Parameters for analog output module
2AO U HF
Range of values
Default setting
Applicability
Group diagnostics (parameter
assignment error, internal
error)
•
Disable
•
Enable
Disable
Module
Diagnostics: Short circuit to M
1
•
Disable
•
Enable
Disable
Channel
Response to CPU/master
STOP
•
No output current or voltage
•
Substitute a value
•
Keep last value
No output current or voltage Module
Type/range of output
•
Deactivated
•
1 to 5 V
•
±10 V
±10 V
Channel
Substitute value
2
To 65,535 (value range must lie
within the nominal range)
•
±10 V: 0 V
±5 V: 0 V
1 to 5 V: 1 V
Channel
1 No diagnostics detection between -0.296 V and +0.296 V
2
If there is no voltage being supplied to the interface module or COMPACT module but the supply to the analog output
modules continues, the substitute values that have been assigned parameters are output. Substitute values must be within
the nominal range. You can assign values from -27,648 to +27,648 as parameters (when assigning parameters using the
GSD file).