![Siemens 2AI 2/4WIRE HF Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/siemens/2ai-2-4wire-hf/2ai-2-4wire-hf_manual_376945025.webp)
Connecting
5.2 Wiring unused channels of the analog input modules
2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0)
Manual, 04/2007, A5E01076111-01
25
5.2
Wiring unused channels of the analog input modules
Rules
Pay attention to the following instructions when wiring unused channels:
●
"Deactivate" unused input channels when assigning parameters.
●
A deactivated channel always returns the value 7FFF
H
.
5.3
Using the shield connection
Rules
To prevent interference we recommend the following for analog electronic modules:
●
Use shielded wires to the sensors and actuators.
●
Lay out the wire shields on the shield connection.
●
Connect the shield connection to the ground bus with low impedance.