Description of Document:

  

This TID provides the procedures to 

replace and set up the Siemens Gas 

Valve Actuator in all AERCO boilers 

featuring double-block and double-

block-and-bleed gas trains.

 

 

Siemens Actuator 

Siemens  

Gas Valve Actuator  

Replacement Kit  

P/N 27086-TAB 

 

Actuator Replacement Kit for AERCO Boilers, P/N 27086-1 

Boilers 

ITEM 

PART NO. 

QTY 

DESCRIPTION 

All AERCO 

Boilers 

(except 

BMK6000) 

12951-4 

Control Box Bushing 

69038 

Actuator, Siemens SKP15.013U1 
 (without POC switch) 

TID-0092 

Instruction Document 

Actuator Replacement Kit for BMK6000 Boilers, P/N 27086-2 

Boilers 

ITEM 

PART NO. 

QTY 

DESCRIPTION 

BMK6000 

(Only) 

12951-4 

Control Box Bushing 

124138 

Actuator, Siemens SKP15.012U1 
(with POC switch) 

TID-0092 

Instruction Document 

 

 

Содержание 27086-TAB

Страница 1: ...ng double block and double block and bleed gas trains Siemens Actuator Siemens Gas Valve Actuator Replacement Kit P N 27086 TAB Actuator Replacement Kit for AERCO Boilers P N 27086 1 Boilers ITEM PART NO QTY DESCRIPTION All AERCO Boilers except BMK6000 1 12951 4 1 Control Box Bushing 2 69038 1 Actuator Siemens SKP15 013U1 without POC switch 3 TID 0092 1 Instruction Document Actuator Replacement Ki...

Страница 2: ...T PROCEDURE 6 Disclaimer The information contained in this manual is subject to change without notice from AERCO International Inc AERCO makes no warranty of any kind with respect to this material including but not limited to implied warranties of merchantability and fitness for a particular application AERCO International is not liable for errors appearing in this manual Nor for incidental or con...

Страница 3: ... the actuator A light which is visible through the lower left transparent portion of the terminal cover indicates when the actuator receives power An optional non adjustable SPDT proof of closure over travel switch signals the closed position after the gas valve has closed An optional SPDT auxiliary switch is adjustable between 40 and 100 of the stroke The adjustment screw and scale are located on...

Страница 4: ...ey driver 5 REPLACEMENT KIT CONTENTS The contents of replacement kits are shown in Tables 1 and 2 below Table 1 Actuator Replacement Kit P N 27086 1 All BMK Except BMK 6000 Boilers ITEM PART NO QTY DESCRIPTION All AERCO Boilers except BMK6000 1 12951 4 1 Control Box Bushing 2 69038 1 Actuator Siemens SKP15 013U1 without POC Switch 3 TID 0092 1 Instruction Document Table 2 Actuator Replacement Kit ...

Страница 5: ...20 VAC 220 VAC OR 460 VAC ARE USED IN AERCO BOILERS IT IS REQUIRED THAT ALL POWER APPLIED TO THESE BOILERS IS REMOVED FIRST BEFORE PERFORMING ANY OF THE PROCEDURES DESCRIBED IN THIS DOCUMENT USE EXTREME CARE WHEN ACCESSING CIRCUITS AND ELECTRICAL CONNECTIONS WITHIN THE EQUIPMENT SERIOUS PERSONAL INJURY OR DEATH MAY OCCUR IF THIS WARNING IS NOT OBSERVED IMPORTANT Observe local requirements and lock...

Страница 6: ... the spring loaded lever under each wire terminal and remove wires 4 Pull all loose wires from out of the wire conduit in the side A spare bushing for the wiring conduit hole is included in the kit in case it is needed 5 Remove the four 4mm Allen bolts that hold the actuator to the valve body Figure 2 and then remove the actuator 6 Install new actuator from replacement kit and affix to valve body ...

Страница 7: ...lt New York 10913 Phone 800 526 0288 Page 7 of 9 Figure 3 Actuator External Features Figure 4 Actuator Wiring Compartment Electrical Ground Screw Wire Terminals Wire Conduit Opening Semi Transparent Cover Transparent Window showing Valve Position Valve Position Indicator Wire Conduits Cover Screw Wire Conduit Opening Actuator P N 69038 Actuator P N 124138 BMK 6000 Only ...

Страница 8: ...ough wire conduit and wire it as follows Wire Terminals 4 5 N N L and L identically to the old actuator Remove dispose of the two wires attached to Terminals 1 and 2 and wire nut and the wire connecting Terminal 3 to the Low Gas Pressure Switch dashed lines Older Actuator Before Replacement P N 124138 BMK 6000 Only Figure 5 Wiring Compartment 9 Disconnect Wire 153 dotted line from Terminal 3 and c...

Страница 9: ... Oritani Dr Blauvelt New York 10913 Phone 800 526 0288 Page 9 of 9 International Inc AERCO International Inc 2015 Change Log Date Description Changed By 11 24 2014 Rev D PIR 839 2 Replace 69171 with 124138 in kit 27086 2 Chris Blair 1 28 2015 Rev E PIR 934 155 Added Figures 5 6 and steps 8 9 to explain how to wire older BMK 6000 Actuators Chris Blair ...