Siemens Gas Valve Actuator Replacement Kit # 27086-TAB Instructions

 

 

Technical Instruction Document 

TID-0092_0E 

 

VD2: 01/28/2014  AERCO International, Inc. 

 100 Oritani Dr. 

  Blauvelt, New York 10913 

 Phone: 800-526-0288  

 

Page 6 of 9

 

7. REPLACEMENT PROCEDURE 

Replacement instructions for the actuator are as follows: 
1.  After ensuring that all electrical power is removed from the boiler, remove boiler side panels 

as necessary to access the actuator. Depending upon the boiler model, the actuator may be 

installed at any angle except upside down. The example shown in Figure 2 is a double-block 

gas train. 

2.  Use a standard Phillips head screwdriver to remove the screw holding the semi-transparent 

wiring compartment cover of the old actuator and make a note of all wire connections. 

3.  After  making  a  note  of  the  wire  connections,  release  the  wires  from  the  connections  by 

pushing down on the spring loaded lever under each wire terminal and remove wires.  

4.  Pull all loose wires from out of the wire conduit in the side. A spare bushing for the wiring 

conduit hole is included in the kit in case it is needed. 

5.  Remove the four 4mm Allen bolts that hold the actuator to the valve body (Figure 2) and 

then remove the actuator. 

6.

  Install  new  actuator  from  replacement  kit  and  affix  to  valve  body  with  4mm  Allen  bolts 

captured in the body of the new actuator. 

 

7.  On all BMK 1.5 – 3000 models, and on BMK 6000 units with the newer actuator shown in 

Figure 4, remove the new actuator cover, punch out the holes in the plastic to accommodate 

the  wiring,  then  insert  the  wires  through  wire  conduit  and  wire  it  identically  to  the  old 

actuator. Skip this step on older BMK 6000 units with the original actuator (which included 

an Auxiliary Switch Adjustment

 

Screw) as shown in Figure 5, and complete Step 8, below. 

 

 

Figure 2: Actuator Installation on Valve Body 

Siemens Actuator 

(P/N 69038 or 

124138) 

VG Series 

Valve Body 

4mm Allen  

Keyed Bolts  

(x4) 

Semi-Transparent 

Wire Compartment 

Cover 

Содержание 27086-TAB

Страница 1: ...ng double block and double block and bleed gas trains Siemens Actuator Siemens Gas Valve Actuator Replacement Kit P N 27086 TAB Actuator Replacement Kit for AERCO Boilers P N 27086 1 Boilers ITEM PART NO QTY DESCRIPTION All AERCO Boilers except BMK6000 1 12951 4 1 Control Box Bushing 2 69038 1 Actuator Siemens SKP15 013U1 without POC switch 3 TID 0092 1 Instruction Document Actuator Replacement Ki...

Страница 2: ...T PROCEDURE 6 Disclaimer The information contained in this manual is subject to change without notice from AERCO International Inc AERCO makes no warranty of any kind with respect to this material including but not limited to implied warranties of merchantability and fitness for a particular application AERCO International is not liable for errors appearing in this manual Nor for incidental or con...

Страница 3: ... the actuator A light which is visible through the lower left transparent portion of the terminal cover indicates when the actuator receives power An optional non adjustable SPDT proof of closure over travel switch signals the closed position after the gas valve has closed An optional SPDT auxiliary switch is adjustable between 40 and 100 of the stroke The adjustment screw and scale are located on...

Страница 4: ...ey driver 5 REPLACEMENT KIT CONTENTS The contents of replacement kits are shown in Tables 1 and 2 below Table 1 Actuator Replacement Kit P N 27086 1 All BMK Except BMK 6000 Boilers ITEM PART NO QTY DESCRIPTION All AERCO Boilers except BMK6000 1 12951 4 1 Control Box Bushing 2 69038 1 Actuator Siemens SKP15 013U1 without POC Switch 3 TID 0092 1 Instruction Document Table 2 Actuator Replacement Kit ...

Страница 5: ...20 VAC 220 VAC OR 460 VAC ARE USED IN AERCO BOILERS IT IS REQUIRED THAT ALL POWER APPLIED TO THESE BOILERS IS REMOVED FIRST BEFORE PERFORMING ANY OF THE PROCEDURES DESCRIBED IN THIS DOCUMENT USE EXTREME CARE WHEN ACCESSING CIRCUITS AND ELECTRICAL CONNECTIONS WITHIN THE EQUIPMENT SERIOUS PERSONAL INJURY OR DEATH MAY OCCUR IF THIS WARNING IS NOT OBSERVED IMPORTANT Observe local requirements and lock...

Страница 6: ... the spring loaded lever under each wire terminal and remove wires 4 Pull all loose wires from out of the wire conduit in the side A spare bushing for the wiring conduit hole is included in the kit in case it is needed 5 Remove the four 4mm Allen bolts that hold the actuator to the valve body Figure 2 and then remove the actuator 6 Install new actuator from replacement kit and affix to valve body ...

Страница 7: ...lt New York 10913 Phone 800 526 0288 Page 7 of 9 Figure 3 Actuator External Features Figure 4 Actuator Wiring Compartment Electrical Ground Screw Wire Terminals Wire Conduit Opening Semi Transparent Cover Transparent Window showing Valve Position Valve Position Indicator Wire Conduits Cover Screw Wire Conduit Opening Actuator P N 69038 Actuator P N 124138 BMK 6000 Only ...

Страница 8: ...ough wire conduit and wire it as follows Wire Terminals 4 5 N N L and L identically to the old actuator Remove dispose of the two wires attached to Terminals 1 and 2 and wire nut and the wire connecting Terminal 3 to the Low Gas Pressure Switch dashed lines Older Actuator Before Replacement P N 124138 BMK 6000 Only Figure 5 Wiring Compartment 9 Disconnect Wire 153 dotted line from Terminal 3 and c...

Страница 9: ... Oritani Dr Blauvelt New York 10913 Phone 800 526 0288 Page 9 of 9 International Inc AERCO International Inc 2015 Change Log Date Description Changed By 11 24 2014 Rev D PIR 839 2 Replace 69171 with 124138 in kit 27086 2 Chris Blair 1 28 2015 Rev E PIR 934 155 Added Figures 5 6 and steps 8 9 to explain how to wire older BMK 6000 Actuators Chris Blair ...

Отзывы: