Siemens Gas Valve Actuator Replacement Kit # 27086-TAB Instructions

 

 

Technical Instruction Document 

TID-0092_0E 

 

VD2: 01/28/2014  AERCO International, Inc. 

 100 Oritani Dr. 

  Blauvelt, New York 10913 

 Phone: 800-526-0288  

 

Page 3 of 9

 

1. INTRODUCTION 

The Siemens electro-hydraulic gas valve actuators are used in combination with VG series gas 

valves to provide safety shut-off control for industrial and commercial burner applications. It is 

featured in all double-block and double-block-and-bleed gas trains used in AERCO boilers.  
The electro-hydraulic actuator consists of a cylinder filled with oil, a piston containing an electric 

oscillating pump, and a relief system. When power is supplied to the actuator, the relief system 

closes,  and  the  pump  moves  oil  from  the  reservoir  into  the  pressure  chamber.  This  action 

causes the piston to move downward in the cylinder, opening the gas valve. When power to the 

actuator  is  interrupted,  the  relief  system  opens  and  the  gas  valve  closes  in  less  than  0.8 

seconds.    A  position  indicator,  visible  through  the  transparent  portion  of  the  terminal  cover, 

shows  the  entire  stroke  range  of  the  actuator.  A  light,  which  is  visible  through  the  lower  left 

transparent  portion  of  the  terminal  cover,  indicates  when  the  actuator  receives  power.  An 

optional,  non-adjustable  SPDT  proof  of  closure  over  travel  switch  signals  the  closed  position 

after the gas valve has closed. An optional SPDT auxiliary switch is adjustable between 40% 

and 100% of the stroke. The adjustment screw and scale are located on the right side in the 

terminal box, and are visible through the transparent portion of the terminal cover. 
 

2. SPECIFICATIONS 

Agency approvals 

As Safety Shut-Off Valve 

UL/429, FM/7400, ANSI 

Z21.21/CGA6.5 C/I 

Power Supply 

Operating Voltage 

110 to 120 VAC + 10% to -15% 

Operating Frequency 

50 to 60 Hz + 6% 

Power Consumption 

3.5 VA 

Duty Cycle 

Continuous 

Operating 
Environment 

Ambient Operating Temperature 

5°F to 140°F (–15°C to 60°C) 

Mounting Position 

Any position except upside down 

Physical 
Characteristics 

Weight 

2.4 lb (1.1 kg) 

Enclosure 

NEMA 1, 2, 5, and 12 for indoor 

use 

Dimensions 

See Figure 1 

Connections 

Conduit Connection 

Two 1/2-inch NPSM threaded 

knock-outs 

Electrical Connection 

Spring loaded terminals for 14 

AWG wires 

Operating 
Characteristics 

Output Force 

100 lbs. (450 N) 

Maximum Stroke 

1 inch (26 mm) 

Opening Time For Maximum 

Stroke 

Varies with valve size, 14 seconds 

for maximum stroke. 

Closing Time 

<0.8 seconds 

Содержание 27086-TAB

Страница 1: ...ng double block and double block and bleed gas trains Siemens Actuator Siemens Gas Valve Actuator Replacement Kit P N 27086 TAB Actuator Replacement Kit for AERCO Boilers P N 27086 1 Boilers ITEM PART NO QTY DESCRIPTION All AERCO Boilers except BMK6000 1 12951 4 1 Control Box Bushing 2 69038 1 Actuator Siemens SKP15 013U1 without POC switch 3 TID 0092 1 Instruction Document Actuator Replacement Ki...

Страница 2: ...T PROCEDURE 6 Disclaimer The information contained in this manual is subject to change without notice from AERCO International Inc AERCO makes no warranty of any kind with respect to this material including but not limited to implied warranties of merchantability and fitness for a particular application AERCO International is not liable for errors appearing in this manual Nor for incidental or con...

Страница 3: ... the actuator A light which is visible through the lower left transparent portion of the terminal cover indicates when the actuator receives power An optional non adjustable SPDT proof of closure over travel switch signals the closed position after the gas valve has closed An optional SPDT auxiliary switch is adjustable between 40 and 100 of the stroke The adjustment screw and scale are located on...

Страница 4: ...ey driver 5 REPLACEMENT KIT CONTENTS The contents of replacement kits are shown in Tables 1 and 2 below Table 1 Actuator Replacement Kit P N 27086 1 All BMK Except BMK 6000 Boilers ITEM PART NO QTY DESCRIPTION All AERCO Boilers except BMK6000 1 12951 4 1 Control Box Bushing 2 69038 1 Actuator Siemens SKP15 013U1 without POC Switch 3 TID 0092 1 Instruction Document Table 2 Actuator Replacement Kit ...

Страница 5: ...20 VAC 220 VAC OR 460 VAC ARE USED IN AERCO BOILERS IT IS REQUIRED THAT ALL POWER APPLIED TO THESE BOILERS IS REMOVED FIRST BEFORE PERFORMING ANY OF THE PROCEDURES DESCRIBED IN THIS DOCUMENT USE EXTREME CARE WHEN ACCESSING CIRCUITS AND ELECTRICAL CONNECTIONS WITHIN THE EQUIPMENT SERIOUS PERSONAL INJURY OR DEATH MAY OCCUR IF THIS WARNING IS NOT OBSERVED IMPORTANT Observe local requirements and lock...

Страница 6: ... the spring loaded lever under each wire terminal and remove wires 4 Pull all loose wires from out of the wire conduit in the side A spare bushing for the wiring conduit hole is included in the kit in case it is needed 5 Remove the four 4mm Allen bolts that hold the actuator to the valve body Figure 2 and then remove the actuator 6 Install new actuator from replacement kit and affix to valve body ...

Страница 7: ...lt New York 10913 Phone 800 526 0288 Page 7 of 9 Figure 3 Actuator External Features Figure 4 Actuator Wiring Compartment Electrical Ground Screw Wire Terminals Wire Conduit Opening Semi Transparent Cover Transparent Window showing Valve Position Valve Position Indicator Wire Conduits Cover Screw Wire Conduit Opening Actuator P N 69038 Actuator P N 124138 BMK 6000 Only ...

Страница 8: ...ough wire conduit and wire it as follows Wire Terminals 4 5 N N L and L identically to the old actuator Remove dispose of the two wires attached to Terminals 1 and 2 and wire nut and the wire connecting Terminal 3 to the Low Gas Pressure Switch dashed lines Older Actuator Before Replacement P N 124138 BMK 6000 Only Figure 5 Wiring Compartment 9 Disconnect Wire 153 dotted line from Terminal 3 and c...

Страница 9: ... Oritani Dr Blauvelt New York 10913 Phone 800 526 0288 Page 9 of 9 International Inc AERCO International Inc 2015 Change Log Date Description Changed By 11 24 2014 Rev D PIR 839 2 Replace 69171 with 124138 in kit 27086 2 Chris Blair 1 28 2015 Rev E PIR 934 155 Added Figures 5 6 and steps 8 9 to explain how to wire older BMK 6000 Actuators Chris Blair ...

Отзывы: