background image

 

 
 

Installation Instructions

Document No. 129-104

October 1, 2013

 

 

Series 2200 Relative Humidity and 
Temperature Room Units For 
APOGEE® Controllers 

 

 

 

Page 1 of 5 

Product Description 

These room units measure relative humidity and 
temperature in the occupied space in which they are 
installed. Models with display allow users to view the 
measured temperature value. A version with 
temperature setpoint adjustment is also offered. 

These devices are intended for use with appropriate 
signal input on an APOGEE Controller. The effective 
sensing range is 32°F to 122°F (0°C to 50°C), and 
the setpoint range is 55°F to 95°F (13°C to 35°C). 

These room units can be mounted on electrical 
boxes, stud-type mounting brackets, or drywall. 
Obtain the necessary mounting hardware and follow 
the appropriate mounting procedures for the type of 
installation required. 

Product Numbers 

QFA3212.FWSN QFA32SS.FWSN 
QFA3212.EWSN QFA32SS.EWSN 

Accessories 

AQA2200-INTL 

Room Unit Back Plate 

 (10-pack) 

AQA2200-2X4 

Room Unit Back Plate 

 (Single) 

563-102 GSKT Kit 

Room Sensor Insulating 

 Gasket 

(10-pack) 

 

(For hollow wall installations) 

NOTE: 

If installing the Back Plate, discard the 
metric screws provided with the Back Plate 
and utilize the Room Unit mounting screws. 

Caution Notations 

CAUTION 

Equipment damage or loss of 
data may occur if you do not 
follow a procedure as 
specified. 

 
Item Number 129-104, Rev. HA 

Expected Installation Time 

20 minutes 

Required Tools 

 

Sizes 1 and 2 Phillips screwdrivers 

 

Small and medium flat-blade screwdrivers 

 

1/16-inch hex key 

 

Medium-duty electric drill 

 

3/16-inch (4.8 mm) drill bit 

 

One-inch (25 mm) hole saw 

 Small 

level 

 Tape 

measure 

 

Marker or pencil 

Prerequisites 

 

Review these instructions before beginning. 

 

Installed: appropriate field wiring within the 
maximum wiring run length for the individual 
equipment controller. The maximum 
recommended length is 750 feet (229 m) for 
18 AWG; 300 feet (91 m) for 22 AWG. 

 

All wiring must comply with National Electric 
Code (NEC) and local regulations. 

 

Figure 1.  Typical Temperature Room Unit. 

Содержание 2200 Series

Страница 1: ...EWSN Accessories AQA2200 INTL Room Unit Back Plate 10 pack AQA2200 2X4 Room Unit Back Plate Single 563 102 GSKT Kit Room Sensor Insulating Gasket 10 pack For hollow wall installations NOTE If installing the Back Plate discard the metric screws provided with the Back Plate and utilize the Room Unit mounting screws Caution Notations CAUTION Equipment damage or loss of data may occur if you do not fo...

Страница 2: ...f the device 3 Cut a 1 inch 25 mm center hole with a hole saw NOTE It is recommended that you use the optional Insulating Gasket on the back of the Sensor Base for hollow wall installations When applying the adhesive backed gasket to the back of the Sensor Base orient the gasket so that the cut out arrow portion of the gasket is in the upper lefthand quadrant of the Sensor Base The Sensor Base has...

Страница 3: ...e back of the PCA SEN0588R1 F C Figure 5 Changing Display to C 3 Snap the room unit cover to the room unit base plate by first hooking the room unit front to the top latches and then rotating the cover downward until it latches 4 Loosen the safety set screw at the bottom of the base one or two revolutions to lock the cover to the base Be careful not to loosen too far as the screw can be completely...

Страница 4: ...or ACH 2 DC or ACN GND 3 Temp Output 4 Humidity Output 5 Passive Temp 6 Passive Temp Common QFA3212 FWSN or QFA32SS FWSN 1 DC or ACH 2 DC or ACN GND 3 Temp Output 4 Humidity Output 5 Passive Temp 6 Passive Temp Common 7 Setpoint Output 8 Override 9 Override Common CAUTION Follow manufacturer s Installation Instructions and Wiring Guidelines for connecting the controller to the Room Unit APOGEE Con...

Страница 5: ...ution Figure 8 Externally AC Powered 2200 Room Units NOTE Externally DC powered 2200 Room Units require isolated DC supply with all commons connected and may be used on the same controller with other Room Units powered by Internal Sensor Supply NOTE Externally AC powered 2200 Room Units require controller common and all AC secondary neutral ACN to be earth grounded and may be used on the same cont...

Отзывы: