4. During the test run, check and document the following:
– Check whether it is running smoothly.
– Document the voltage, current and power values. As far as possible, document the
corresponding values of the driven machine.
– If this is possible using the available measuring equipment, check the bearing and stator
winding temperatures until they have reached steady-state values.
– Check the machine for noise or vibrations on the bearings or bearing shields as it runs.
5. In case of uneven running or abnormal noise, switch off the machine. As the machine runs
down, identify the cause.
– If the mechanical operation improves immediately after the machine is switched off, then
the cause is magnetic or electrical.
– If the mechanical running does not improve immediately after switching the machine off,
then the cause is mechanical.
- Imbalance of the electrical machine or the driven machine
- The machine set has not been adequately aligned
- The machine is being operated at the system resonance point. System = motor, base
frame, foundation, ...
NOTICE
Serious damage to the machine
If the vibration values in operation are not maintained in accordance with DIN ISO
10816-3, then the machine can be mechanically destroyed.
● During operation, observe the vibration values in accordance with DIN ISO 10816‑3.
NOTICE
No-load operation without cantilever force
Never operate motors with cylindrical roller bearings in no-load operation without any
cantilever force Otherwise, this could damage the bearings.
7.7
Set values for monitoring the bearing temperature (optional)
Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7-1
Set values for monitoring the bearing temperatures before commissioning
Set value
Temperature
Alarm
115 °C
Shutting down
120 °C
Commissioning
7.7 Set values for monitoring the bearing temperature (optional)
SIMOTICS M-1PH8 1PH818., 1PH822.
Operating Instructions 07/2016
89
Содержание 1PH818
Страница 2: ...18 07 2016 14 04 V14 00 ...
Страница 12: ...Introduction SIMOTICS M 1PH8 1PH818 1PH822 12 Operating Instructions 07 2016 ...
Страница 28: ...Description SIMOTICS M 1PH8 1PH818 1PH822 28 Operating Instructions 07 2016 ...
Страница 48: ...Preparations for use 4 14 Converter operation SIMOTICS M 1PH8 1PH818 1PH822 48 Operating Instructions 07 2016 ...
Страница 82: ...Electrical connection 6 4 Auxiliary circuits SIMOTICS M 1PH8 1PH818 1PH822 82 Operating Instructions 07 2016 ...
Страница 100: ...Operation 8 10 Faults SIMOTICS M 1PH8 1PH818 1PH822 100 Operating Instructions 07 2016 ...
Страница 126: ...Spare parts 10 9 Speed encoder type 1PH818 1PH822 SIMOTICS M 1PH8 1PH818 1PH822 126 Operating Instructions 07 2016 ...
Страница 136: ...Quality documents SIMOTICS M 1PH8 1PH818 1PH822 136 Operating Instructions 07 2016 ...
Страница 163: ...D 3 Operating instructions of the EC external fan SIMOTICS M 1PH8 1PH818 1PH822 Operating Instructions 07 2016 163 ...
Страница 197: ...AA Manual STROMAG Break AC Manual Ziehl Abegg external fan ...
Страница 198: ...Siemens AG Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY www siemens com drives ...