NOTICE
Connecting the temperature sensors
Temperature sensors may be connected only to intrinsically safe circuits with certified
evaluation devices. The maximum permissible input currents and powers according to the
prototype test certificate may not be exceeded. This can otherwise result in damage.
If shielded, intrinsically safe temperature sensors are fitted or mounted, they must be
connected using the blue connecting terminals. The cable shield is grounded just once;
multiple grounding is not permitted.
6.4.7
Installing intrinsically safe circuits
There must be potential equalization along the entire length of the intrinsically safe electrical
circuits when intrinsically safe circuits are involved.
A stranded wire is used as the potential equalizing cable. A copper braided strip is used to
ensure potential equalization between the cable entry plate and the terminal box enclosure.
Table 6-3
Electrical data
Non-intrinsically safe electric circuit V
m
= 700 V alternating voltage
Intrinsically safe power circuit in "fail-safe" type of protection
Ex ib IIB/IIC, only connected to certified intrinsically safe circuits that are galvan‐
ically isolated from ground.
Maximum values for total:
IIB
IIC
e.g. with T4: V
i
= 28 V
V
i
= 24 V
I
i
= 300 mA
I
i
= 170 mA
P
i
= 1.3 W
P
i
= 1.3 W
The effective internal inductance and capacitance are negligibly small.
The intrinsically safe circuits are safely galvanically isolated from all non-intrinsically safe
circuits up to a peak value for the rated voltage of 1000 V. Please refer to the additional plate
on the machine for the maximum values for "intrinsically safe power circuits".
Electrical connection
6.4 Connecting the auxiliary circuits
SIMOTICS HV C 1NB1402-2AA84-4CA0-Z
Operating Instructions 06/2018
67
Содержание 1NB1402-2AA84-4CA0-Z
Страница 2: ...26 06 2018 15 34 V3 00 ...
Страница 10: ...Table of contents SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 10 Operating Instructions 06 2018 ...
Страница 22: ...Description SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 22 Operating Instructions 06 2018 ...
Страница 84: ...Operation 8 9 Faults SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 84 Operating Instructions 06 2018 ...
Страница 110: ...Disposal 11 4 Disposal of components SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 110 Operating Instructions 06 2018 ...
Страница 112: ...Service and Support SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 112 Operating Instructions 06 2018 ...
Страница 117: ...117 ...
Страница 118: ...118 ...
Страница 119: ...119 ...
Страница 120: ...120 ...
Страница 121: ...121 ...
Страница 122: ...122 ...
Страница 123: ...123 ...
Страница 124: ...124 ...
Страница 125: ...125 ...
Страница 126: ...126 ...
Страница 127: ...127 ...
Страница 128: ...128 ...
Страница 129: ...129 ...
Страница 130: ...130 ...
Страница 131: ...C 2 Declaration of conformity SIMOTICS HV C 1NB1402 2AA84 4CA0 Z Operating Instructions 06 2018 131 ...
Страница 132: ...Quality documents C 2 Declaration of conformity SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 132 Operating Instructions 06 2018 ...
Страница 133: ...133 ...
Страница 148: ...148 ...
Страница 150: ...Additional documents SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 150 Operating Instructions 06 2018 ...
Страница 154: ...Index SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 154 Operating Instructions 06 2018 ...
Страница 155: ...AF Einbauerklärung Loher LDX U157 AJ EC Declaration of Conformity U161 ...