● System-dependent conditions, such as ambient temperature, routing type, cable cross-
section as defined by required length of cable, etc.
● Requirements according to IEC/EN 60204‑1
● Requirements according to IEC/EN 60079‑14
Use only sealing plugs, cable entries and conductor entries, that are certified and marked for
use in the respective hazardous area (the zone).
6.5.2
Bringing cables into the auxiliary terminal box and routing them
The required data for connecting the auxiliary circuits is located on the terminal diagram on
the inside of the respective auxiliary terminal or terminal box cover.
● In some cases a terminal strip is installed in the main terminal box for the auxiliary circuit
connections.
● The required stripped length on conductors for auxiliary terminals differs according to
terminal type (6 to 9 mm). When the length is correct, the conductor should reach the stop
in the terminal and at the same time the conductor insulation should reach the contact part
of the terminal.
Adapting the cable glands
A plate is bolted to the terminal box enclosure via a rectangular cutout through which the
connecting cables enter. The plate is generally delivered with threaded holes and cable glands.
1. Open the auxiliary terminal box and undo the cable entry plate screws.
2. For the undrilled version, drill the required number of holes or threads in the required size
of the cable gland into the cable entry plate.
3. Mark the cables if necessary for subsequent assignment.
4. Pull the cables through the cable glands and the cable entry plate, and connect the cables.
5. Fit the cable entry plate.
6. Make sure that the seal on the screwed sockets for the cable glands satisfies the degree
of protection.
See also
Tightening torques for screw and bolt connections (Page 145)
Spare parts (Page 125)
Electrical connection
6.5 Connecting the auxiliary circuits
SIMOTICS TN Series N-compact 1LA8
Operating Instructions 05/2014
77
Содержание 1LA8
Страница 2: ...23 05 2014 10 18 V8 00 ...
Страница 12: ...Table of contents SIMOTICS TN Series N compact 1LA8 12 Operating Instructions 05 2014 ...
Страница 14: ...Introduction 1 1 About these instructions SIMOTICS TN Series N compact 1LA8 14 Operating Instructions 05 2014 ...
Страница 60: ...Assembly 5 3 Installing the machine SIMOTICS TN Series N compact 1LA8 60 Operating Instructions 05 2014 ...
Страница 88: ...Start up 7 7 De energizing SIMOTICS TN Series N compact 1LA8 88 Operating Instructions 05 2014 ...
Страница 100: ...Operation 8 11 faults SIMOTICS TN Series N compact 1LA8 100 Operating Instructions 05 2014 ...
Страница 173: ...AC Declaration of conformity 1LA8 area 22 AA KE NSR _1LA8_1PQ8_1PP8_1LP8 ...