General Information Regarding the Wiring
Hardware Description 0360520xx
73
11.4
Cables for the Rotor Position Detection
Use shielded lines and shielded Submin D shells for wiring the different measuring
systems. The shield must be connected to the Submin D shell at the servo module
side and to the housing of the measuring system.
Examples for the use of conductors:
X
Motors with resolver
LIYCY 3 x 2 x 0.14 or 4 x 2 x 0.14 for motors with integrated thermal contact.
Conductors: shielded, twisted in pairs. Twist mode: sine/sine, cosine/cosine, ro-
tor/rotor and, if necessary, thermal contact/thermal contact.
For delicate applications we recommend to additionally shield the separate
pairs.
X
Motors with incremental encoder
LIYCY 5 x 0.14 or 7 x 0.14 for motors with integrated thermal contact
X
Motors with Hall effect sensor and tacho generator
LIYCY 9 x 0.14 or 12 x 0.14 for motors with integrated thermal contact.
11.5
Cables for External Ballast Resistors
The cables of the external ballast resistor of R
EX
and +UB must be twisted. If the ca-
ble is longer than 20 cm a shielded cable must be used.
Содержание sinudyn-0360520 Series
Страница 7: ...Symbols 6 Symbols...
Страница 13: ...Safety Instructions and Application Advice 12 Safety Instructions Application Advice...
Страница 15: ...Unit Assembly Complying EMC 14 EMC...
Страница 53: ...Functional Description of the Connectors Interfaces 52 Hardware Description 0360520xx sinudyn 36...
Страница 59: ...Specification of the Digital Inputs and Outputs 58 Hardware Description 0360520xx sinudyn 36...
Страница 75: ...General Information Regarding the Wiring 74 Hardware Description 0360520xx...
Страница 93: ...Appendix Manufacturers 92 List of Manufacturers...