![SIEB & MEYER 0362171DA1 Series Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/sieb-and-meyer/0362171da1-series/0362171da1-series_hardware-description_1264945044.webp)
Status Display and Error Messages
8
Status Display and Error
Messages
The 7-segment display shows status and error messages.
A status message is made up of 1 to 5 digits and displayed as sequence. All messages
end with dot behind the last digit. When the first digit is 'E.', there is a permanent error.
If the cause of an error can be specified, the display indicates the actual error code fol-
lowed by a hyphen and a one-digit sub error code.
Note
Devices with older firmware do not feature the sub error code.
Examples:
1.
Permanent display 0
▸
Controller is switched off.
▸
No error.
2.
Permanent display 1
▸
Controller is switched on.
▸
No error.
3.
Permanent display 1.
▸
Controller is switched on.
▸
No error.
▸
Dot calls additional attention to PI limit.
4.
→
→
Sequential display
▸
Controller is switched off due to error E40.
▸
The error is not present anymore.
5.
→
→
Sequential display
▸
Controller is switched off due to error E40.
▸
The error is still present (indicated by the dot be-
hind 'E').
6.
→
→
→
→
Sequential display
▸
Controller is switched off due to error E11.
▸
The error is still present (indicated by the dot be-
hind 'E').
▸
Sub error code 4 is indicated as cause.
7.
→
→
Sequential display
▸
Controller is in boot loader mode: Display appears
short-time when the device is booted and when
the system software is loaded.
8.
→
→
Sequential display
▸
Drive address: During booting of the devices the
set address of the drive is displayed short-time
(here A01)
8.1
List of the Operating States
Code
Description
0
Ready to switch on
1
Controller active
1.
Controller active, controller is limited / PI limit
2
Mains 'Ready for operation' not present yet
L
Boot loader active (during boot / software load)
44
Drive Amplifier SD2B plus - 0362171DA1xxxx, 0362171DB1xxxx