Configuration
8.2
Internal restart interlock
The configuration of the restart interlock is defined by the wiring that is in place during the
first or last teach-in process performed.
How to activate the internal restart interlock:
⋅
Make the electrical connections for the reset button (see section 5.3 on page 33).
⋅
Switch on the V200/V300.
⋅
Perform a teach-in procedure.
If there is no signal on the
Reset/restart
input, then the safety camera system will
activate the internal restart interlock and save this configuration in the device. The
device is now waiting for the reset button to be pressed.
⋅
Check the effectiveness of the protective device as described in section 7.1 “Test
notes” on page 42.
How to deactivate the internal restart interlock:
⋅
Permanently connect the
Reset/restart
input to 24 V (see section 5.2 on page 33).
⋅
Switch on the V200/V300.
⋅
Perform a teach-in procedure.
If 24 V are present on the
Reset/restart
input, the safety camera system will deactivate
the internal restart interlock and save this configuration in the device.
⋅
Check the effectiveness of the protective device as described in section 7.1 “Test
notes” on page 42.