Electrical installation
•
To meet the requirements of the relevant product standards (e.g. IEC 61
496-1), the
external voltage supply for the devices (SELV) must be able to bridge a brief mains
failure of 20 ms. Power supplies according to EN 60
204-1 satisfy this requirement.
Suitable power supplies are available as accessories from SICK (see section 12.2
“Accessories” on page 59).
5.1
System connection M12
×
8
The V200/V300 has a hard-wired cable (length: approx. 30 cm) with a cable plug M12
×
8.
Pin
Colour
Signal
Function
1
White
RESTART
Reset/restart (optional)
2
Brown
+24 V DC
24 V DC (voltage supply)
3
Green
TEACH/SYNC
Teach-in/synchronisation
4
Yellow
EDM
External device monitoring (EDM) (optional)
5
Grey
OSSD1
OSSD1 (safe output signal switching
device 1)
6
Pink
OSSD2
OSSD2 (safe output signal switching
device 2)
7
Blue
GND
0 V DC (voltage supply)
8
–
FE
Functional earth
Connecting cables of different length are available as accessories from SICK (see
section 12.2 “Accessories” on page 59). If you use connecting cables you have assembled
yourself, ensure the functional earth (pin 8) is connected.
Fig. 20: System connection
V200/V300
Tab. 10: Pin assignment
system connection
V200/V300