6
Electrical installation
6.1
Important notes
WARNING
Risk of injury and damage caused by electrical current!
Due to equipotential bonding currents, incorrect earthing can lead to the following
dangers and faults: Voltage is applied to the metal housing, cable fires due to cable
shields heating up, the product and other devices become damaged.
■
Generate the same ground potential at all grounding points.
NOTICE
Equipment damage due to incorrect supply voltage!
•
Only operate the device with the specified supply voltage.
•
Please read the notes on electrical installation.
The connection of the network and IO-Link cable of the SIM200 must be voltage-free
(U
V
= 0 V). The following information must be observed, depending on the connection
type:
■
Even when the wiring is looped through, the total current of the module must not
exceeded 4 A.
■
An incorrect supply voltage may result in damage to the device. Operation is only
permitted in a short-circuit protected system with max. 8 A.
■
Only apply voltage/switch on the voltage supply (U
V
> 0 V) once all electrical
connections have been established.
6.2
Preparing the electrical installation
To carry out the electrical installation, you will need:
•
Connection cables for the peripheral devices, including the corresponding data
sheets
•
Voltage supply cable
•
If customers assemble the cables: crimping tool, ferrules, soldering iron, and other
installation material
6.3
Assembling the cables (optional)
For a list of cables suitable for use with the device, see:
.
Customer assembly of the cables is only necessary in special cases. Ensure a sufficient
length of cable is provided, e.g. for strain-relief clamps.
NOTICE
Risk of damage/malfunction due to incorrect PIN assignment
Incorrect wiring of the male connectors/female connectors can lead to damage to or
malfunctions in the system.
■
Observe data sheets provided by the cable manufacturer.
■
Observe the pin assignment.
6
ELECTRICAL INSTALLATION
16
O P E R A T I N G I N S T R U C T I O N S | SIM200
8026126//2020-10-15 | SICK
Subject to change without notice