Electrical installation
¾
Connect the outputs as shown in
.
Note
If the "Device Ready" function is chosen, the CLX outputs a static pulse in Reading mode.
For connecting the host interface via the AMV/S60 Connection Module, see the Operating
Instructions for the "
AMV/S60 Connection Module
" (no. 8008296).
Tip
The output function, pulse duration (timer), and polarity of the signals can be changed on
the D
EVICE
C
ONFIGURATION
tab in the "CLV-Setup" program.
¾
Click the R
ESULT
O
UTPUT
P
ARAMETERS
button and enter the values in the dialog box dis-
played.
Perform a download to the CLX.
Recommondation
¾
To check the switching functions using a high-impedance digital voltmeter, connect a
load to the outputs to prevent incorrect voltage values/switching statuses from being
displayed.
Output
Result X
CLX "I/O" connection
Pin Y
AMV/S60
Terminal Z
Result 1
Pin 4
T. 31
Result 2
Pin 8
T. 32
Result 3
Pin 10
T. 33
Result 4
Pin 15
T. 34
Table 5-22: Pin and terminal assignment for "Result 1 to Result 4" switching outputs
Switching mode
PNP-switching with respect to the supply voltage V
S
Properties
The current in the event of a short-circuit is limited to 0.7 A
Function
assignment
(default)
Result 1: Device Ready (static), polarity: not inverted
Result 2: Good Read (100 ms), polarity: not inverted
Result 3: No Read (100 ms), polarity: not inverted
Result 4: Match 1 (100 ms), polarity: not inverted
Electrical values
0 V
≤
V
outr
≤
30 V
Guaranteed: V
out
≤
V
S
–1.3 V with I
out
≤
100 mA
I
out
≤
100 mA
Table 5-23: Characteristic data of the "Result 1 to Result 4" switching outputs