Input (= I), Output (=
O), Power (= P)
4
Axis 1; B+
I
5
Encoder GND (= voltage supply GND = housing
GND)
-
6
Axis 2; A+
I
7
Axis 2; B+
I
8
AUX in; +
I
9
Axis 0; A-
I
10
Axis 0; B-
I
11
Axis 1; A-
I
12
Axis 1; B-
I
13
Axis 2; A-
I
14
Axis 2; B-
I
15
AUX in; -
-
6.4
Connecting device electrically
Important information
NOTICE
Observe the wiring instructions,
see "Wiring instructions", page 28
Approach
1.
Ensure the voltage supply is not connected.
2.
Connect the device according to the connection diagram.
3.
To secure the male connectors, tighten the screws.
4.
Connect the cable to the periphery.
Further topics
•
6.5
Connecting voltage supply
Prerequisites
•
The device is set up or mounted.
•
The device is electrically connected.
•
If the device is brought from a cold to a warm environment, wait until the cold
device has reached room temperature. Depending on air humidity and room tem‐
perature, this process can take up to three hours.
•
Use a suitable separate power supply unit,
.
Approach
1.
To establish the voltage supply, connect the control unit to the power supply unit.
2.
To secure the male connector, tighten the screws.
✓
The
device status
LED lights up green.
3.
Before starting a measurement, check the device settings (e.g. measuring rate,
averaging). Reconfigure the device if necessary.
ELECTRICAL INSTALLATION
6
8027188//2022-05-25 | SICK
O P E R A T I N G I N S T R U C T I O N S | OD7000
33