To teach in a switching point, the device must be able to measure. The distance to the
object must not change during teach-in. The object must be in the measuring range.
Setting switching point manually
Set the distance of the switching point manually,
see "Adjust the value", page 23
. The
value of the switching point can be set depending on the set number of decimal places.
Adjustable parameters
•
Q1 SP1 teach-in (manual)
•
Q1 SP2 teach-in (manual)
7.4.3.2
Single point output mode (SP1:DtO)
Set a switching point. If the measured distance value falls below (N/O contact:
High-
active
switching point logic) or exceeds (N/C contact:
Low-active
switching point logic) the
switching point, a signal is output (change of output level).
Minimum
1
Maximum
3
2
1
0
Figure 11: Distance to object, single switching point (N/O contact: High-active, PNP)
1
Minimum
2
Switching point
3
Maximum
Minimum
1
Maximum
3
2
1
0
Figure 12: Distance to object, inverted simple switching point (N/C contact: Low-active, PNP)
1
Minimum
2
Switching point
3
Maximum
Selecting output mode and setting parameters
>
Q1 Output
>
>
Q1 Mode
>
>
Q1 Single point (SP1:DtO)
>
>
Q1 Output
>
> Parameter >
> Select option, teach-in or set value >
Parameter
Value
Factory setting
Q1 SP1 teach-in (auto)
OD2000-
030
:
-5.04 mm ... +5.75 mm
OD2000-
050
:
-10.10 mm ... +11.50 mm
OD2000-
245
:
-176.75 mm ... +189.00 mm
OD2000-
350
:
-252.50 mm ... +271.00 mm
OD2000-
700
:
-505.00 mm ... +550.00 mm
0.00 mm
Q1 SP1 teach-in (manual)
7
OPERATION
32
O P E R A T I N G I N S T R U C T I O N S | OD2000