Use
Protocol
Source
Source port
Target
Destination port
EtherNet/IP
(Explicit Messaging)
TCP
EtherNet/IP client
Selected by the
EtherNet/IP client
microScan3
44818
microScan3
44818
EtherNet/IP client
Selected by the
EtherNet/IP client
EtherNet/IP (ListI‐
dentity via UDP)
UDP
EtherNet/IP client
Selected by the
EtherNet/IP client
microScan3 or Lim‐
ited Broadcast or
Directed Broadcast
44818
microScan3
44818
EtherNet/IP client
Selected by the
EtherNet/IP client
EtherNet/IP (cyclic
data transmission,
implicit messaging,
unicast)
UDP
Originator (e.g. con‐
troller or micro‐
Scan3 Pro I/O)
2222
Target (micro‐
Scan3)
2222
Target (micro‐
Scan3)
2222
Originator (e.g. con‐
troller or micro‐
Scan3 Pro I/O)
2222
CoLa2 (protocol
from SICK, configu‐
ration and diagnos‐
tics)
TCP
CoLa2 client, e.g.
computer with
Safety Designer
Selected by CoLa2
client
microScan3
2122
microScan3
2122
CoLa2 client, e.g.
computer with
Safety Designer
Selected by CoLa2
client
CoLa2 (protocol
from SICK, device
search)
UDP
Computer with
Safety Designer
30718 … 30738
microScan3 or Lim‐
ited Broadcast or
Directed Broadcast
30718
microScan3
30718
Computer with
Safety Designer (if
in the same subnet)
or Broadcast (if in a
different subnet)
30718 … 30738
Data output in
transmit mode
con‐
tinuous
UDP
microScan3
Randomly selected
Target computer
Configurable
4.5.2
Integration of the safety laser scanner into the network
DANGER
Danger due to unintended use of SIL 2 data of the safety laser scanner in SIL 3
applications
b
Ensure that the safety-related data of the safety laser scanner is only used in
applications which do not exceed safety integrity level SIL 2 (IEC 61508) of the
safety laser scanner.
b
Before integrating an already-configured safety laser scanner into a safety-related
network: reset the safety laser scanner to its factory settings,
.
Addressing
The safety laser scanner needs a unique IP address, the sub-network mask and,
possibly, the IP address of the router to be able to exchange data with other devices in
the network.
As long as no configuration has been transferred to the device, you can change the
network settings via a network connection without logging in to the device.
4
PROJECT PLANNING
74
O P E R A T I N G I N S T R U C T I O N S | microScan3 Pro I/O
8025424/1ELL/2022-01-21 | SICK
Subject to change without notice