Operating instructions IO-Link Master IOLG2PN-03208R01 – PROFINET
Technical data
46
© SICK AG • Presence Detection • Subject to change without notice • 8018665.10RD
11.2 Power supply
Supply voltage
DC 18 V … 30.2 V
Connection
7/8” male connector, 5-pin
Functional grounding
1 FE connection for M4 ground strap
Current consumption at 24 V DC
130 mA
Residual ripple
< 1%
Input ports/output ports
8 x M12 female connector, 5-pin, A-coded
Table 22: Supply
11.3 PROFINET
PROFINET port
2 x 10Base-/100Base-Tx
PROFINET port connection
2 x M12-female connector, 4-pin, D-coded
Data transmission rate
10 / 100 Mbit/s
Suitable cable types in accordance
with IEEE 802.3
Screened, twisted cable pair, at least STP CAT5 or
STP CAT5e
Max. cable length
100 m
Flow control
Half duplex / full duplex (IEEE 802.33x-Pause)
Table 23: PROFINET
11.4 Ambient conditions
Mark of conformity
CE
EMC
EN 61000-6-2
EN 61000-6-4
Ambient temperature range
• Operation: –5 °C … +70 °C
• Storage: –25 °C … +70 °C
Enclosure rating (IEC 60529)
IP 67 when plugged in and screwed together
Shock resistance
EN 60068-2-27
Vibration resistance
EN 60068-2-6, EN 60068-2-64
Table 24: Ambient conditions