6.2
Pin assignment of the connections
M12 connection, CANopen: 1116319
1
2
4
3
5
PIN
Pin assignment
1 - BN
VIN
2 - WH
CAN HIGH
3 - BU
GND
4 - BK
reserved - do not connect
5 - GY
CAN LOW
M12 connection, RS485: 1114008
1
2
4
3
5
PIN
Pin assignment
1 - BN
VIN
2 - WH
RS485 A
3 - BU
GND
4 - BK
reserved - do not connect
5 - GY
RS485 B
6.3
Connecting the supply voltage
The sensor must be connected to a voltage supply with the following properties:
•
Supply voltage DC 10.8 V ... 30 V (stabilized safety extra-low voltage (SELV/PELV)
as per current standard EN 60950-1)
•
Power source with at least 3 W power
Protecting the supply cables
To ensure protection against short-circuits/overload in the customer’s supply cables,
the wire cross-sections used must be appropriately selected and protected.
The following standards must be observed in Germany:
•
DIN VDE 0100 (part 430)
•
DIN VDE 0298 (part 4) and/or DIN VDE 0891 (part 1)
Electrical connection of GLS100
•
Ensure the voltage supply is not connected.
•
Turn the swivel connector into the desired position.
•
Connect the sensor according to the connection diagram.
6
ELECTRICAL INSTALLATION