78
FLOWSIC200 · Operating Instructions · 8013271/1CJ9/V2-0/2022-01 · © SICK Engineering GmbH
Commissioning and parameterization
4.2.10
Output flow direction
To output the flow direction, the measuring range must be set in a negative and a positive
range in the “Configuration / I/O Configuration / Analog Output / Analog Outputs” directory.
The zero point then lies between the two end values. Falling below or exceeding the zero
point can additionally be signaled with the limit value relay (
Example:
Measuring range: -20 ... +20 m/s
The Live zero value (= lower end value) corresponds to a physical value of -20 m/s, the
20 mA value (= upper end value) corresponds to a physical value of +20 m/s.
With Live zero = 4 mA, the zero point is at 12 mA.
Fig. 65
Directory “Configuration / I/O Configuration / Analog Output / Analog Outputs”
Optionally, only the amount of the measured value can be output. For this purpose, the
“Write absolute value” checkbox must be activated.
NOTICE:
The limit value relay must be configured when the absolute value is output,
otherwise no signaling of falling below or exceeding the zero point is possible.
Содержание FLOWSIC200
Страница 1: ...O PERATING INSTRU CTIO NS FLOWSIC200 Flow Velocity Monitor Installation Operation Maintenance...
Страница 30: ...30 FLOWSIC200 Operating Instructions 8013271 1CJ9 V2 0 2022 01 SICK Engineering GmbH Product description...
Страница 100: ...100 FLOWSIC200 Operating Instructions 8013271 1CJ9 V2 0 2022 01 SICK Engineering GmbH Commissioning and parameterization...
Страница 104: ...104 FLOWSIC200 Operating Instructions 8013271 1CJ9 V2 0 2022 01 SICK Engineering GmbH Maintenance...
Страница 121: ...Specification FLOWSIC200 Operating Instructions 8013271 1CJ9 V2 0 2022 01 SICK Engineering GmbH 121...