Fieldbus gateways
Module specific
alarms
Error code
Transition
emergency
state chart
Emergency error code
Error register
M1…M5
Error
history
SDO 1003
Gateway detected
incoming error as per
trigger conditions
–
1
FF01h
81h
M1 = Module index
M2…M5 = Module
diagnostics data
M2, M3, M4,
M5
See Tab. 105.
Gateway detected
outgoing error, other
errors are present
–
2
FF02h
81h
M1 = Module index
M2…M5 = Module
diagnostics data
M2, M3, M4,
M5
See Tab. 105.
Gateway detected
incoming error, other
errors are present
–
3
FF03h
81h
M1 = Module index
M2…M5 = Module
diagnostics data
M2, M3, M4,
M5
See Tab. 105.
All errors cleared
–
4
0000h
00h
M1 = 0
M2…M5 = 0
–
Tab. 131: Error objects overview
6.2.13
CANopen diagnostics examples
Example 1: XTIO module on position 1, output Q4 stuck at high
The gateway sends an emergency message (see Tab. 104).
CAN ID
DLC DATA
08C
8
03 FF 01 01 40 00 00 00
The gateway’s CANopen address is 12 (= C hex). The XTIO module has the position 1 in the
Flexi Soft system.
08C:
Identifier (80 + C)
8:
Data length code: 8 bytes follow.
03FF: Error code FF03: device specific error
01:
Error register 01 of SDO 1001H
01:
Module index M1: module in position 1
40:
Module status bit 30 (bit 6 of byte M2) = 1: output 4 stuck at high (see Tab. 105)
Reading the current error from SDO 3100:
PLC request:
CAN ID
DLC DATA
60C
8
40 00 31 02 00 00 00 00
60C:
Identifier (600 + C)
8:
Data length code: 8 bytes follow.
40:
Expedited upload request
00 31: Index 3100
02:
Subindex 02: module in position 1 (see Tab. 125)