6
Electrical installation
6.1
Safety
WARNING
Electrical voltage
There is a risk of injury from electrocution while connecting the devices.
b
Disconnect the power for the entire plant/machine.
WARNING
Unintended start of the plant/machine
The plant/machine could inadvertently start while you are connecting the devices.
b
Disconnect the power for the entire plant/machine.
NOTICE
Enclosure rating IP20 only applies if the front connector is mounted.
6.2
Device connection
Prerequisites
Electrical connection requirement:
•
Electrical installation is performed in accordance with EN 60204-1.
•
The mounting rail is connected to the functional earth.
•
The voltage supply and connected signals meet the requirements for extra-low
voltages with safe separation (EN 60664) or NEC Class 2 (UL 1310).
•
The external voltage supply must be capable of buffering brief power failures of
20 ms as specified in EN 60204-1. Suitable power supply units are available as
accessories from SICK.
•
The GND of all connected devices must have the same potential as A2 of the main
module. Exceptions are actuators which are connected to an expansion module
with its own voltage supply.
•
The GND connections of the actuators to the safety outputs are in star formation
with the GND connection of the voltage supply.
Pin assignment
Q2
Q4
Q6
Q8
A2
I2
I4
I6
I8
Q1
Q3
Q5
Q7
A1
9
11
13
15
17
10
12
14
16
18
5
7
3
4
6
8
1
2
I1
I3
I5
I7
Figure 8: Terminals on front connector
ELECTRICAL INSTALLATION
6
8024583/2020-11-10 | SICK
O P E R A T I N G I N S T R U C T I O N S | Flexi IO XTDO1
19
Subject to change without notice