Address
Contents
Data type
Size
781
Service number (internal
use)
ASCII
STRING
4 words (8 bytes)
13.3.2.1.6
Project data
Overview
Contains the project data from the configuration software of the safety controller.
Project data
Table 176: Project data
Address
Contents
Data type
Size
800
Device name
UTF8
STRING
32 words (64 bytes)
832
Project name
UTF8
STRING
32 words (64 bytes)
864
Application name
UTF8
STRING
32 words (64 bytes)
896
User name
UTF8
STRING
32 words (64 bytes)
928
Description
UTF8
STRING
50 words (100 bytes)
Complementary information
•
Unused characters in the STRING are padded with blanks.
•
If the description is longer than 100 bytes, the content is truncated.
13.3.2.1.7
Find me function
Table 177: Find me function
Address
Contents
Size
1000
Find me function
0: Standard operation of the LEDs
1: Flash mode for 30 seconds
1)
1 word (2 bytes)
1)
A change from 1 to 0 ends the flash mode.
13.3.2.2
SLMP output data
13.3.2.2.1
Process data to the safety controller
Process data to the safety controller
Table 178: Process data to the safety controller
Address
Contents
Size
50
Process data
1 word (2 bytes)
...
1 word (2 bytes)
74
1 word (2 bytes)
Complementary information
•
The process data are written and read dynamically. You can write or read 25 words
(50 bytes) of process data at address 50. You can write or read 24 words
(48 bytes) of process data from address 51 onwards.
TECHNICAL DATA
13
8024589/2020-11-10 | SICK
O P E R A T I N G I N S T R U C T I O N S | Flexi Compact
145
Subject to change without notice