When relevant?
Description
Value [ms]
When using dual-channel safety out‐
put Q.
For one or both safety outputs:
•
1 ms
A potential switch-off delay in the event of
a fault applies to the second safety output
1)
:
•
Without the
Increased capacitive loads
allowed
option: 5 ms
•
With the
Increased capacitive loads
allowed
option: 50 ms
1
Fast shut off is used.
0.5 ms
–
Total
1
1)
If switch-off occurs, a single safety output (Q) may be switched on rather than switched off for this time in
the event of an internal hardware error. An undesired switch-on can also occur in the switched off state
and is limited to 5 ms by a fault switch-off. Ensure, in particular for single-channel safety outputs, that the
resultant pulse does not result in a safety-critical state of the system.
Table 155: Calculating the maximum response time – signal path 1
Components of
the calculation
Description
Value [ms]
1. Inputs
Response time of the
observed input in the
signal path
IN1, IN3, IN4 or IN5
•
3
2. Logic
a) Response time
of the main module
logic
2 × logic execution time
Take the value from the report in the
configuration software.
8
Delay due to logic application (e.g.
switch-on delay or switch-off delay
function block)
Take the value from the report in the
configuration software.
b) Response time of
the routing
For OUT3 output to the gateway only
No delay time
0
c) Response time of
the fast shut off logic
No delay time
0
3. Outputs
Response time of the
observed output in
the signal path
OUT1, OUT2, OUT3, OUT4 or OUT5
•
1
Total
12
Response time of signal path 2
Table 156: IN1 – Response time of safety capable inputs (I)
When relevant?
Description
Value [ms]
Always
Input processing time
3
ON-OFF debounce filter is configured. Min. debounce filter time
Take the value from the report in the con‐
figuration software.
–
Input element is connected to a test
output (X).
Max. tolerated test pulse delay
Take the value from the report in the con‐
figuration software.
–
13
TECHNICAL DATA
136
O P E R A T I N G I N S T R U C T I O N S | Flexi Compact
8024589/2020-11-10 | SICK
Subject to change without notice