Chapter
3
Operating instructions
Flexi Classic
34
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
8011509/YPP0/2015-10-26
Subject to change without notice
Product description
=
Also pay attention to the lamp on output Q2 (“Global emergency stop status”, “Reset
required”) on the related UE410-GU.
Q1
I1/I2
I3/I4
I
P
I
N
Lamp Q2
Cause
ν
Ν
ν
Ν
Ν
ν
A local emergency stop has been
triggered on this station.
ν
Ν
X
ν
X
Ν
A previous station has triggered a
global emergency stop.
ν
Ν
X
X
ν
Ν
A next station has triggered a global
emergency stop.
ν
ν
X
X
X
⌠∏
A global emergency stop has been
triggered on this station.
ν
Ν
Ν
Ν
Ν
∏
Reset is required on this station.
Ν
Ν
Ν
Ν
Ν
ν
The safety output on the module is
active and the system enabled.
A combination of several causes may occur, e.g. if a local emergency stop and a global
emergency stop have been triggered.
LED I5 and I6 indications
In normal operation with safety output Q1 active the LEDs I5 and I6 are
ν
Off
.
LED
Meaning
I5 illuminates
Ν
Green
The safety output Q1 is shut down, the external actuators
have dropped out. Otherwise check the wiring.
I5 flashes
∏
Green
EDM error. Check the wiring. If necessary, replace the
actuator.
I6 illuminates
Ν
Green
The reset button is pressed. Otherwise check the wiring.
I6 flashes
∏
Green
The reset button has been operated for too long. Check the
wiring if necessary.
Also note the description of the LED indicators on the UE410-GU in section 3.4.1 “Controls
and status indicators” on page 28 as well as chapter 10 “Diagnostics” on page 93.
Fig. 10: Diagnostic displays
on the UE410-GU
Tab. 15: Diagnostics on the
UE410-GU
Ν
The LED or lamp is
illuminated constantly.
∏
The LED or lamp is
flashing (1 Hz).
⌠∏
The LED or lamp is
flashing (2 Hz).
ν
The LED or lamp is off.
X
Any
Note
Tab. 16: Significance of the
diagnostics LEDs I5 and I6 on
the UE410-GU
LED I3/I4: sensor with local
action
LED Q1: safety output Q1
LED I1/I2: emergency stop
pushbutton with global action
LED I
P
: status of all previous
modules
LED I
N
: status of all next
modules