16.3
Checklist for initial commissioning and commissioning
Checklist for manufacturers or installers for installing electro-sensitive protective
device (ESPE)
The details relating to the items listed below must be available no later than when the
system is commissioned for the first time. However, these depend on the specific appli‐
cation (the requirements of which must be reviewed by the manufacturer or installer).
This checklist should be retained and kept with the machine documentation to serve as
reference during recurring tests.
This checklist does not replace the initial commissioning, nor the regular inspection by
qualified safety personnel.
Have the safety rules and regulations been observed in compliance with the
directives and standards applicable to the machine?
Yes
⃞
No
⃞
Are the applied directives and standards listed in the declaration of conformity? Yes
⃞
No
⃞
Does the protective device comply with the required PL/SIL claim limit and PFHd
in accordance with EN ISO 13849-1/EN 62061 and the required type in accor‐
dance with EN 61496-1?
Yes
⃞
No
⃞
Is access to the hazardous area or hazardous point only possible through the
protective field of the ESPE?
Yes
⃞
No
⃞
Have appropriate measures been taken to protect (mechanical protection) or
monitor (protective devices) any persons or objects in the hazardous area when
protecting a hazardous area or hazardous point, and have these devices been
secured or locked to prevent their removal?
Yes
⃞
No
⃞
Are additional mechanical protective measures fitted and secured against
manipulation which prevent reaching below, above or around the ESPE?
Yes
⃞
No
⃞
Has the maximum shutdown and/or stopping time of the machine been mea‐
sured, specified and documented (at the machine and/or in the machine docu‐
mentation)?
Yes
⃞
No
⃞
Has the ESPE been mounted such that the required minimum distance from the
nearest hazardous point has been achieved?
Yes
⃞
No
⃞
Are the ESPE devices properly mounted and secured against manipulation after
adjustment?
Yes
⃞
No
⃞
Are the required protective measures against electric shock in effect (protection
class)?
Yes
⃞
No
⃞
Is the control switch for resetting the protective devices (ESPE) or restarting the
machine present and correctly installed?
Yes
⃞
No
⃞
Are the outputs of the ESPE (OSSDs or safety outputs via the network) inte‐
grated according to the required PL/SILCL in accordance with EN ISO
13849-1/EN 62061 and does the integration correspond to the circuit dia‐
grams?
Yes
⃞
No
⃞
Has the protective function been checked in compliance with the test notes of
this documentation?
Yes
⃞
No
⃞
Are the specified protective functions effective at every operating mode that can
be set?
Yes
⃞
No
⃞
Are the switching elements activated by the ESPE, e.g. contactors, valves, moni‐
tored?
Yes
⃞
No
⃞
Is the ESPE effective over the entire period of the dangerous state?
Yes
⃞
No
⃞
Once initiated, will a dangerous state be stopped when switching the ESPE on or
off and when changing the operating mode, or when switching to another pro‐
tective device?
Yes
⃞
No
⃞