4.4
Integration in electrical control
Overview
This chapter contains important information about integration in the electrical control.
Information about the individual steps for electrical installation of the device:
"Electrical installation", page 41
.
Important information
DANGER
Hazard due to lack of effectiveness of the protective device
In the case of non-compliance, it is possible that the dangerous state of the machine
may not be stopped or not stopped in a timely manner.
b
Make sure that the following control and electrical requirements are met so that
the product can fulfill its protective function.
Requirements for use
The output signals of the protective device must be analyzed by downstream controllers
in such a way that the dangerous state of the machine is ended safely. Depending
on the safety concept, signal evaluation is carried out e.g. with safety relays or with a
safety controller.
•
It must be possible to electrically influence the control of the machine.
•
The electrical control of the machine must meet the requirements of IEC 60204-1.
•
A restart interlock must be implemented depending on applicable national regula‐
tions or required reliability of the safety function. Because the protective device
does not have an integrated restart interlock, this must be implemented in the
external control, if required.
•
When using a safety controller, different signal levels of both OSSDs must be
detected depending on applicable national regulations or required reliability of the
safety function. The maximum discrepancy time tolerated by the controller must
be selected according to the application
•
The OSSD1 and OSSD2 output signals must not be connected to each other.
•
In the machine controller, the signals of both OSSDs must be processed sepa‐
rately.
Figure 14: Dual-channel and isolated connection of OSSD1 and OSSD2
4
PROJECT PLANNING
22
O P E R A T I N G I N S T R U C T I O N S | deTec2 Core
8014276/1DCM/2022-10-27 | SICK