Configuration
4
Configuration
The C4000 Select supports several advanced functions which are configured using DIP
switches. Included in these advanced functions are beam coding, extended I/O capability
and floating blanking. The DIP switches used for configuration are located under the
plastic cover in the system connection end cap.
You must ensure electrostatic discharge does not occur when handling the C4000
Select!
Before handling the C4000 Select, you must ensure that any electrostatic charge is dis-
charged. An electrostatic discharge that occurs on the C4000 Select may cause damage
to the electronic boards.
The following figure and table describe the C4000 Select sender unit DIP switch settings:
Beam code 1
Beam code 2
Description
OFF
OFF
No beam coding (uncoded)
ON
OFF
Beam code 1 enabled
OFF
ON
Beam code 2 enabled
ON
ON
No beam coding (uncoded)
Additional information regarding the scanning range can be found in section 4.2 “Beam
coding” on page 23.
The following figure and table describe the C4000 Select receiver unit DIP switch settings:
High range select
Description
OFF
Scanning range set to low range (0…7.5 m)
ON
Scanning range set to high range (5…21 m)
Additional information regarding the scanning range can be found in section 4.3 “Scanning
range” on page 25.
WARNING
Fig. 11: C4000 Select sender
unit DIP switch
Tab. 4: C4000 Select sender
unit DIP switch settings
Fig. 12: C4000 Select recei-
ver unit DIP switches
Tab. 5: C4000 Select recei-
ver unit DIP switch settings
for high range
1 = Beam code 1 select
2 = Beam code 2 select
1 = High range select
2 = Extended I/O enable
1 = Beam code 1 select
2 = Beam code 2 select
3 = Floating blanking enable
4 = One beam floating blanking select
5 = Two beam floating blanking select
ON position